JX2-PROFI1
1 Safety Instructions
Jetter AG
12
1.3
Device Specific Prevention of Risks
1.3.1
Connecting Two PROFIBUS Participants
1.3.2
The Use of Specific Connectors
Danger
If two PROFIBUS participants being distant from each other are to be connected,
please make sure they have got the same potential.
Danger
Only connectors specified as PROFIBUS connectors may be used, as they
should already have been equipped with the terminating resistor, which can be
activated with the help of a special switch.
For baud rates that are greater than 1.5 MBaud, specific PROFIBUS connectors
for the reduction of cable capacitances must be applied.
Only use cables which have been specified as cable type A in the PROFIBUS
Standard EN 50 170.
The maximum cable lengths defined in the PROFIBUS Standard EN 50 170 must
be maintained.
Содержание JetWeb JX2-PR0FI1
Страница 1: ...Article 608 641 01 November 2002 Printed in Germany ...
Страница 4: ...JX2 PROFI1 Table of Contents Jetter AG 4 ...
Страница 13: ...1 Safety Instructions JetWeb 13 Jetter AG ...
Страница 14: ...JX2 PROFI1 2 Physical Dimensions Jetter AG 14 2 Physical Dimensions Fig 2 Front View JX2 PROFI1 ...
Страница 15: ...JetWeb 15 Jetter AG Fig 3 Side View JX2 PROFI1 Fig 4 Top View JX2 PROFI1 ...
Страница 19: ...JetWeb 19 Jetter AG ...
Страница 21: ...JetWeb 21 Jetter AG ...
Страница 23: ...JetWeb 23 Jetter AG 5 3 Features ...
Страница 43: ...JetWeb 43 Jetter AG ...
Страница 45: ...JetWeb Jetter AG 45 ...
Страница 61: ...JetWeb Jetter AG 61 43 rPB_DiagData1 12146 44 rPB_DiagData2 12147 45 46 rPB_DataIn 12300 47 rPB_DataOut 12400 ...
Страница 62: ...JX2 PROFI1 8 Sample Programs 62 Jetter AG ...
Страница 63: ...JX2 PROFI1 Appendices Jetter AG 63 Appendices ...