Digit 35 — Refrigeration Accessories
0 = Moisture Indicating Sight Glass -
The sight glass shows if the liquid line has a full line of
liquid or if it has bubbles which shows it’s a liquid/vapor mix. It should not be used to determine
proper charge. The moisture indicator shows if the system is dry or if it has harmful moisture
content.
A = Moisture Indicating Sight Glass + Compressor Isolation Valves –
In addition to the
Moisture Indicating Sight Glass, ball type Compressor Isolation Valves
are mounted on the cooling
circuit discharge and suction lines permitting isolation of the compressor for service or replacement.
The valves are located close to the compressors. The valve works through a quarter turn from open
to closed. Teflon seals and gaskets are used with a nylon cap gasket to prevent accidental loss. This
option reduces the amount of refrigerant that must be recovered during compressor service or
replacement since closing these valves isolates the compressor.
B = Moisture Indicating Sight Glass + Replaceable Core Filter Driers -
In addition to the
Moisture Indicating Sight Glass,
Replaceable Core Filter Driers allow for easy changeout of the
filter-drier element.
C = Moisture Indicating Sight Glass + Replaceable Core Filter Compressor Isolation
Valves
Digit 36 — Water Connection
0 = Grooved Pipe Connection, Standard Header Length
A = Grooved Pipe Connection, Extended Header Length –
To provide additional spacing
beyond the standard ¾” between modules,
t
he Grooved Pipe Connection, Extended Header Length
Kit consists of grooved pipe couplings and spacer pipe to allow for easy installation of water
manifold units.
D = No Header Piping (Heat Exchangers Only) –
When chiller is used in standalone operation
(i.e., single module) an array header is not necessary. It is a cost savings to use the 6” array header
only when needed for array applications or it is desirable to keep field piping to a minimum. Field
piping can be connected to heat exchangers instead of factory provided header.
Figure 1 - No Header, Heat Exchangers Only Configuration
Содержание FWCD Series
Страница 1: ...FWCD Series Chillers Installation Operation Maintenance...
Страница 2: ...Jetson www JetsonHVAC com 2...
Страница 29: ...Jetson www JetsonHVAC com 29 Dimensions Dimensions Figure 3 FWCD dimensions brazed plate condenser...
Страница 30: ...Jetson www JetsonHVAC com 30 Figure 4 FWCD array dimensions brazed plate condenser...
Страница 31: ...Jetson www JetsonHVAC com 31 Figure 5 FWCD dimensions shell and tube condenser...
Страница 32: ...Jetson www JetsonHVAC com 32 Figure 6 FWCD array dimensions shell and tube condenser...
Страница 33: ...Jetson www JetsonHVAC com 33 Figure 7 FWCD dimensions remote condenser...
Страница 34: ...Jetson www JetsonHVAC com 34 Figure 8 FWCD array dimensions remote condenser...
Страница 36: ...Jetson www JetsonHVAC com 36 Figure 10 Clearance FWCD array chiller application all condenser options...
Страница 82: ...Jetson www JetsonHVAC com 82 Wiring Figure 26 FWCD wiring schematic...
Страница 83: ...Jetson www JetsonHVAC com 83 Figure 27 FWCD wiring schematic continued...
Страница 84: ...Jetson www JetsonHVAC com 84 Figure 28 FWCD dual circuit secondary wiring schematic...
Страница 85: ...Jetson www JetsonHVAC com 85 Figure 29 FWCD dual circuit secondary wiring schematic continued...
Страница 86: ...Jetson www JetsonHVAC com 86 Figure 30 Field wiring FWCD single unit single circuit...
Страница 87: ...Jetson www JetsonHVAC com 87 Figure 31 Field wiring FWCD single unit dual circuit...