13
Commissioning
- Turn gas supply OFF, remove inlet pressure test point screw and connect a suitable pressure
gauge.
- Turn gas supply ON - check installation for gas soundness.
Burner Operation (Manual)
- Push the control knob in and turn anti-clockwise until the spark igniter operates.
- Repeat this operation to purge any air from the system until the pilot ignites.
- Keep the knob pushed in for 10-12 secs to energise the flame failure device.
- Release the knob, the pilot should remain alight.
- Depress the knob slightly and turn anti-clockwise as far as it will go to the MAX position. The fire
should light.
- Check the setting pressure - 20.0 mb ± 1.0 mb (cold) MAX.
- Check for gas soundness at all joints with leak detection fluid.
- Turn the appliance OFF
Ɣ
and turn off the gas supply to the fire.
- Remove the pressure gauge and replace the pressure test point screw.
- Check the pressure test point for gas soundness with the gas supply turned ON.
Burner Operation (Remote Control)
- If Remote Control fitted, point the handset to the sensor at the front of the fire. Push and hold the
two ignition buttons together, on the left hand side of the handset. The fire will give out a beep
sound and you can release the buttons. After a few seconds you will hear the clicking spark to the
pilot light. Once the pilot is lit the fire main burner will come on to the high position (this whole
process will take no more than 20 seconds).
- If the burner fails to light repeat this operation to purge any air from the system until the pilot and
main burner ignites.
- Check the setting pressure - 20.0 mb ± 1.0 mb (cold) MAX.
- Check for gas soundness at all joints with leak detection fluid.
- Turn fire off by pointing the handset at the sensor and push the top left button. The fire will go out.
- Remove the pressure gauge and replace the pressure test point screw.
- Check the pressure test point for gas soundness with the gas supply turned ON.
Spillage Check (Fig. 7)
- Close all doors and windows in the room containing the fire.
- Light the fire as described in the User Instruction and turn control knob to MAX.
- Wait for 5 minutes.
- Introduce a smoke match and position it so that the tip is 20mm under the fireplace opening.
- Traverse the full width of the fireplace opening keeping the smoke match horizontal.
- NB It is recommended that the smoke match is fitted into a smoke match holder when checking
for clearance of combustion products.
- Ensure that most of the smoke is drawn into the flue aperture.
If in doubt wait a further 10 minutes and repeat the test.
- If there is a fan/extractor fitted in the property turn it full on and open all inter-connecting doors.
- The spillage test must now be repeated.