Jetmaster 1050 DS Скачать руководство пользователя страница 9

Page 8

4. Clearance requirements -

Hebel installation double sided

Fill entire cavity up to the outer
casings with 100mm R3.5 fibreglass
insulation to 200mm above the top
of the gather

The appliance and Flue Combination should be installed at the following clearances:

• The mantle shelf clearances should be 1000mm above as per clause 3.4.1.3(b) of AS/NZS 2918:2018

• The fronts and sides of enclosure must consist of 75mm Hebel PowerPanel.

• The Hebel PowerPanel sides of the enclosure can be placed against the appliance with 100mm R3.5 insulation compressed to

50mm either side of the air box between the PowerPanel and the appliance.

• The Hebel PowerPanel front walls must be installed minimum of 25mm from the appliance gather with 100mm R3.5 insulation

compressed to 25mm between the appliance and Hebel PowerPanel.

• The appliance front wall, the gather, sides and all other external parts of the appliance must be wrapped in 100mm R3.5 insulation

between the PowerPanel enclosure up to the height of 200mm above the top of the gather.

• The Flue penetration through the ceiling must have a 50mm gap in all directions around the outer casing of the flue from

combustibles and minimum ventilation of 158,788mm2 through the ceiling.

• The front walls of the enclosure must be made of Hebel PowerPanel to a height of 1280mm above the hearth and must extend to

75mm either side of the appliance.

• The first internal wall noggin at the front of the appliance can sit on the top of the PowerPanel enclosure.

• Internal Noggins must not be closer than 50mm from the outer flue casing.

• The External side wall of the PowerPanel Enclosure can be placed against a combustible wall.

75mm Hebel powerpanel
against insulation and firebox
air box - compress 100mm
R3.5 insulation to 50mm

500mm

500mm

610mm

Timber header on edge

above Hebel/Brick box.

50mm clearance to flue

required.

Non-com cladding
only to Hebel box

1050 Unit will be recessed on
both sides by 50mm using
75mm Hebel Powerpanel.

Use supplied 70mm surround to
cover insulation.

Fig 3.7

Содержание 1050 DS

Страница 1: ...el only Other fuels may over fire and generate poisonous gases i e carbon monoxide Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may caus...

Страница 2: ...11 6 General use Attaching firescreen lighting a fire 12 6 General use Fuels Cleaning Maintenance Safety 12 AS NZS 2918 2018 General notes Thank you for purchasing a Jetmaster fireplace Please read this manual carefully to ensure the correct installation There are different methods of installing a Jetmaster fireplace depending on the unit size Before conducting any works please go to the relevant ...

Страница 3: ...g devices Over drafting caused by excessive chimney heights Ideal performance is with height of chimney minimum 4 6 metres as per AS NZS 2918 2018 Negative pressure results from the imbalance of air available for the appliance to operate properly It can be strongest in lower levels of the house Causes include Exhaust fans kitchen bath etc Range hoods Combustion air requirements for furnaces water ...

Страница 4: ...quate flow of outdoor air for all combustion appliances and exhaust equipment Ensure cental heating and air conditioning return vents are not located in the vicinity of the appliance Avoid installing the appliance near doors walkways or small isolated spaces Recessed lighting should be a sealed can design Attic hatches weather stripped or sealed Attic mounted duct work and air handler joints and s...

Страница 5: ...hick welded steel it is normal and expected for some imperfections and slightly out of square components It is recommended to not begin construction of cavity or flue penetration points until after the unit is in place on site 50mm 1050DSU 105mm 700DSU Gather must be securely bolted to the unit Optional 3 and 4 sided 70mm surrounds are available to fill in between unit and outer Hebel box Add 40mm...

Страница 6: ... as a reference only Due to the nature of thick welded steel it is normal and expected for some imperfections and slightly out of square components It is recommended to not begin construction of cavity or flue penetration points until after the unit is in place on site 2 Components and specifications Optional 100mm surround The surround should be the last item installed The wall cavity must be com...

Страница 7: ...ation Note Timber framing should be constructed using normal framing methods Image above is an example only Do not install finishing materials around the cavity until after the fireplace has been installed Frame height is from top of the 100mm hebel hearth base Refer to the following page for hearth requirements ...

Страница 8: ...tector Hebel blocks must be used in front of the appliance base on both sides when installing the appliance see joint AS NZS 2918 2018 3 3 2 The floor protector should extend 500mm in front of each of the appliance openings and be placed centrally in the 1450mm width 100mm thick floor protector projection can consist of multi layered non combustible materials 700 DSU unit Hearth A minimum 610mm de...

Страница 9: ... wrapped in 100mm R3 5 insulation between the PowerPanel enclosure up to the height of 200mm above the top of the gather The Flue penetration through the ceiling must have a 50mm gap in all directions around the outer casing of the flue from combustibles and minimum ventilation of 158 788mm2 through the ceiling The front walls of the enclosure must be made of Hebel PowerPanel to a height of 1280mm...

Страница 10: ...nation cap away from trees adjacent structures uneven roof lines and other obstructions Your local dealer is the expert in your geographic area and can usually make suggestions or discover solutions that will easily correct your flue problem Minimum height of flue system exit Solid fuel AS NZS 2918 2018 NOTICE Chimney performance may vary Trees buildings roof lines and wind conditions affect perfo...

Страница 11: ...cond length to have crimp facing down Fig 5 2 Glass tape may be required to ensure a snug fit The outer flue is then installed outside active flue with crimp facing up to ensure water penetration on flue above roof runs out Rivet active flues together at crimped joins Fix outer non active flues to active inner flues use 3 x 25mm self tapping screws through outer flue at bottom at each join and on ...

Страница 12: ...t side towards you with the steel handle provided 2 In firebox lay your fire lighters 10 to 15 centimetres apart depending on the size of your firebox Do not use newspaper as a fire lighter On units that are installed with a dual spigot gather it is recommended to light 2 fires directly underneath the two separate flues 3 Add soft wood kindling in a criss cross pattern above the firelighters Softw...

Страница 13: ...AS NZS 2918 General notes Fuels The quality of firewood is extremely important How long a tree has been felled or dead for does not indicate how dry the wood is The best way to dry wood is to split it and expose the inner core allowing the sun to dry the wood naturally Good wood merchants will split the wood for you but may not season it for you The amount of you pay for your wood does not justify...

Отзывы: