a.
If using a square tubing arrangement it is recommended to have this
advised by a structural engineer
b.
Consult a structural engineer to ensure that the structural beams,
tubes/plates are rated to uphold the respective fan weights.
c.
Fan installation area must be free of obstructions such as lights, cables,
sprinklers, or other structures. The fan blades should have at least 250mm
of clearance from any obstructions, vertical and horizontal.
d.
Adhere to the safety requirements in the table below when selecting the
fan location.
e.
The fan should be visible from the location of the wall controller. The
mounting structure must be able to withstand the torque forces
generated by the fan.
Safety Requirement Minimum Distances
Clearance
Minimum 250mm from all fan parts. The fan installation area
must be free of obstructions such as light, cables, sprinklers,
or other building structure.
Blade height
At least 3 meters above the finished floor level
Fan spacing
As specified by Jet Black Fans, or 4 x fan diameter, centre-to-
centre.
50 x 50 Square tube install