Technical Information 
Wind / Rain Sensor- automatic 
Type: W+RE B/4 
 

 

Date of Issue: Dec 13  

 

 

 

 

 

 

 

       Page 4 of 6  

 

 

 

 

 

 

 

Handbook 

– Jet Cox Ltd 

 

Jet Cox Ltd / Coxdome, CRH House, Prothero Ind Est, Bilport Lane, Wednesbury, WS10 0NT   Tel: 0121 530 4230 Email: [email protected] 

Valid from date of issue until the next edition. This document / drawing is protected by copyright.  

The recipient may use it only for the propose for which it was entrusted to him. 

 

Operation / Function 

 

Change- over switch from the 

‘central CLOSE / Automatic’ to the ‘Automatic’ position 

 

Activation by rain: 

In case of activation by the rain sensor all actuators close. 
The two-colour diagnosis LED lights red (steady light). 
 

Remark: 

The ventilation switches are locked for the period of the rain activation. 
The activation resets 10 or 20 min. (adjustable) after the last sensor actuation. 
A change over to ventilation switch mode is still possible in case of activation (see manual mode). 
 

Manual mode (timed ventilation): 

The rain activation can be deactivated by actuating the manual button (in front of the housing). 
Despite a rain activation the actuators can be 

‘OPENED’ via the ventilation switches. 

The two-colour diagnosis LED flashes green. 
The rain activation is active again after the expiry of approx. 30 min. or after pressing the manual switch again. 
 

Change-over switch from the 

‘central CLOSE / Automatic’ to the ‘central CLOSE’ position 

 

The two-colour diagnosis LED lights red (steady light). 
CLOSED mode is a steady signal with priority over all other operating modes. 
All functions are locked. 

 

An external central CLOSE switch (potential-free N/O contact) can be closed. 

 

 

Forwarding of a wind-rain activation 

 

An external group extension or display (max. 60W) can be connected to the terminal X2. 
In case of activation, 230Volt with maximum amperage of 280mA will be switched. 
L1 = steady contact 

 
 

Settings: 

 

Various wind-rain parameters and operating modes can be set by means of the installed DIP switches. 

 

DIP switch settings for the wind speed 

 

 

Test 

approx. 

3 m/s 

approx. 

4 m/s 

approx. 

6 m/s 

approx. 

8 m/s 

approx. 

10 m/s 

approx. 

12 m/s 

approx. 

14 m/s 

Switch 1 

off 

on 

off 

on 

off 

on 

off 

on 

Switch 2 

off 

off 

off 

off 

on 

on 

on 

on 

Switch 3 

off 

off 

on 

on 

off 

off 

on 

on 

 

Attention:  After start-up make all necessary settings for wind speed  

Factory setting = test setting. 

Recommended setting is 8 m/s

 

 

Remark:  

In the test setting, the activation and release delay is deactivated. 

 

DIP switch settings for wind-rain release delay 

 
The wind-rain signal is stored for approx. 10 or 20 minutes (adjustable). 
 
 

Switch position OFF 

Switch position ON 

Switch 4   =   Wind-rain release delay 

10 minutes 

20 minutes 