We reserve the right to change designs and technical specifications of our products
.
Rev 8.1 Oct-15 Page
19
/
42
The following settings are for experienced engineers only. Incorrect configuration of these
settings can cause the equipment not to function correctly, and may cause damage to the
equipment, system or property.
#
Menu Item
Function
Default
Value
16 PUMPS NUMBER
The number of pumps installed in the pressurisation unit.
This can be set to either 1 or 2.
2
17
PUMP TYPE
The type of pump installed in the pressurisation unit.
There are two options, which are as follows:
0 – Centrifugal Pump (Flexfiller /Digifiller/ Midi)
1 – Piston Pump (mini units only)
1
18
PUMP SENSE
Disabling this option will stop the controller from monitoring the pumps and
generating <PUMP FAIL> faults.
It is not recommended to disable this option. Please consult Flamco Technical
before doing so.
YES
19
SENSOR TYPE
The type of pressure sensor installed in the unit.
There are two options which are as follows:
1 – 1-6V Output, 0-10 Bar Range
2 – 1-6V Output, 0-16 Bar Range
1
20
SPC
CONTROLLER
Not required on standard Pressurisation unit
NO
21
ADDITIVE
Not required on standard Pressurisation unit
NO
22
ID NUMBER
A user configurable identification number.
This option does not serve any functional purpose.
01
23
RELAY
INVERSION
When enabled, all normally open fault contacts (i.e. all except the common
alarm) are converted to normally closed.
NO
24
OVERRUN
Allows the pump to continue running for a set period of time after the required
pressure has been reached.
This will prevent the pumps from ‘hunting’.
The value can be set from 0 – 10 seconds.
5
25
PRESSURE
ALARM AUTO
RESET
When enabled, the <HIGH PRESSURE> and <LOW PRESSURE> alarms will be
cleared automatically if and when the pressure returns to normal.
If disabled, the alarms must be manually reset.
YES
26
CASCADE
Allows the pumps to operate in duty/assist mode.
After either pump starts, the other pump will start after a set period of time.
This option can be set to OFF, or 5 – 30 seconds.
OFF
27
BOOST
When enabled, the controller will allowing the pumps to run even if the system
pressure is zero.
YES
28
SOLENOID
CONTROLLER
When enabled, the “high water” input is used to trigger a top up solenoid valve
connected to the “sensor healthy” volt free contact.
This option should only be enabled on units which utilize a solenoid valve as the
means of top-up.
NO
Note:
21 = GLYCOL UNIT / 28 = FLOMAT ON (>7.3 VERSION CONTROLLER)