![Jesco GW 702 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/jesco/gw-702/gw-702_operating-manual_644919021.webp)
Relays | Operating Manual GW 702 | 21
Instead of the measured value display, the display indicates "Erase Alarm, press key
".
With key
the alarm is acknowledged manually and the relay is switched.
NOTE!
Through the manual acknowledgement only the relay is switched. The alarm message is still displayed until
the cause of alarm has been eliminated.
10.2 Configuration
Measured value display
Main menu
Preselect M1/2
Limit value 1/2
0.09 ppm 0.01 ppm
Sens. 1 Sens. 2
Preselect M1
Preselect M2
Enter password
Sensor test
Basic settings
Service
Sensor Info
Limit value 1
Limit value 2
Turn-on delay
Limit value 1
ppm
Basic settings
Select Alarm
Value 1/2 Sens. 1/2
Sensor 1
Sensor 2
Analogue output
Language
No. of RS 485
Select Alarm
Alarm Sens.Test
Value 1 Sens. 1
Value 2 Sens. 1
Value 1 Sens. 2
Value 2 Sens. 2
Direction
Value 1 Sens. 1
Off
Direction
Direction
Alarm = Rel On
Limit values
Setting under measured value display
Main menu
Preselect M1/2
Limit value 1/2
Delay per sensor for limit value 2
Fixed delay time between exceeding the limit value and switching the relay.
Setting under measured value display
Main menu
Preselect M1/2
Limit value 1/2
Relay 3 ("Alarm") allocation
Setting under measured value display
Main menu
Basic Settings
Select Alarm
Value 1/2 Sens
1/2
Alarm Sensor Test Allocation
Activation of relay 3 with unsuccessful sensor test under Main Menu
Basic Settings
Select Alarm
Direction
You determine with the direction, whether relay 3 is normally open (make contact, N.O.) and closes in case
of an alarm or vice versa (break contact, N.C.). In the second case the relay is held active in its normal posi-
tion. This way an alarm is raised even during a power failure.
10.3 Relay Test
Manual test of the relays under measured value display
Service
Relay Test
Test Rel. 1/2/3
Содержание GW 702