
11
Rear Wall Venting
1. Mark the wall at the center of the cabinet opening.
2. Check for obstructions before marking the vent hole location.
Mark a horizontal line 8
³⁄₁₆
" (20.8 cm) from the floor. Mark a
vertical line up to a maximum of 2¼" (7.9 cm) from the right
side of the cabinet centerline.
3. Draw and cut a 6¼" (15.8 cm) diameter hole.
4. Position blower motor in cabinet opening. Connect vent
system to blower motor outlet using a vent clamp.
5. Mount blower motor to the floor with 4 - #8 x ¾" hex head
screws provided.
6. Go to the “Make Gas Connection” section.
Floor Venting
1. Mark the floor at the center of the cabinet opening.
2. Position template on floor by matching the centerline of the
template to the centerline drawn on the floor and place
template 2¼" (5.7 cm) from the back wall.
3. Determine the correct position for the vent hole, depending
on obstructions (joists) in the floor.
The hole can be cut anywhere within the boundaries of either
hatched area.
Option 1: If using the back hatched area (bigger one), the
blower inlet must face the left side as shown on the template.
Option 2: If using the front hatched area (smaller one), the
blower inlet must face the back.
A. Maximum 2¼" (7.9 cm) from
the right of center
B. 8
³⁄₁₆
" (20.8 cm) from floor
A. 6¼" (15.8 cm)
Top View
A. 18¾" (47.6 cm) maximum from back
wall forward into cabinet opening
B. Inlet
C. Vent system
D. Vent clamp
E. Wall vent
A
B
A
A
B
C
D
E
Top View
Top View
Option 1
Option 2
A. Inlet from range
B. Exhaust outlet
A
A
B
B
Содержание W10526082A
Страница 28: ...28 Notes ...