8
Electrical Requirements: U.S.A. Only
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine
that the ground path and wire gauge are in accordance with
local codes.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that
the ground path is adequate.
Do not use an extension cord.
Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/
NFPA 70 — latest edition — and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
WARNING:
Improper connection of the equipment-grounding
conductor can result in a risk of electric shock. Check with a
qualified electrician or service technician if you are in doubt as
to whether the appliance is properly grounded. Do not modify
the power supply cord plug. If it will not fit the outlet, have a
proper outlet installed by a qualified electrician.
Electrical Connection
To properly install your range, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■
Range must be connected to the proper electrical voltage
and frequency as specified on the model/serial/rating plate.
The model/serial/rating plate is located under the console
on the right-hand side. Refer to the illustrations in “Product
Dimensions” in the “Location Requirements” section.
■
This range may be manufactured with a 4-wire power
supply cord or may not include a power supply cord. If your
range does not include a power supply cord, use a 4-wire
power supply cord rated at 250 volts, 40 or 50 amps, and
investigated for use with ranges.
Range Rating*
Specified Rating of Power
Supply Cord Kit and
Circuit Protection
120/240 Volts 120/208 Volts
Amps
Range Size
8.8–16.5 kW
7.8–12.5 kW
40 or 50**
30" (76.2 cm),
36" (91.4 cm)
16.6–22.5 kW
12.6–18.5 kW
50
48" (121.9 cm)
* The NEC calculated load is less than the total connected load
listed on the model/serial/rating plate.
** If connecting to a 50-amp circuit, use a 50-amp rated cord
with kit. For 50-amp rated cord kits, use kits that specify use
with a nominal 1
3
/
8
" (3.5 cm) diameter connection opening.
■
A circuit breaker is recommended.
■
Wire sizes and connections must conform with the rating
of the range.
■
The Tech Sheet is located behind the kick plate in a clear
plastic bag.
If connecting to a 4‑wire system:
This range is manufactured with the ground connected to the
cabinet. The ground must be revised, so the green ground wire
of the 4-wire power supply cord is connected to the cabinet.
See the “Electrical Connection: U.S.A. Only” section.
Grounding through the neutral conductor is prohibited for
new branch-circuit installations (1996 NEC), mobile homes,
recreational vehicles, or an area where local codes prohibit
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a
matching UL Listed, 4-wire, 250-volt, 40- or 50-amp, range
power supply cord must be used. This cord contains four copper
conductors with ring terminals or open-end spade terminals
with upturned ends, terminating in a NEMA Type 14-50R plug
on the supply end.
The fourth (grounding) conductor must be identified by a green
or green/yellow cover and the neutral conductor by a white
cover. Cord should be Type SRD or SRDT with a UL Listed strain
relief and be at least 4 ft (1.22 m) long.
The minimum conductors sized for the copper 4-wire power
cord are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-10 green grounding
If connecting to a 3‑wire system:
Local codes may permit the use of a UL Listed, 3-wire, 250-volt,
40- or 50-amp range power supply cord (pigtail). This cord
contains three copper conductors with ring terminals or open-
end spade terminals with upturned ends, terminating in a NEMA
Type 10-50P plug on the supply end. Connectors on the
appliance end must be provided at the point the power supply
cord enters the appliance. This uses a 3-wire receptacle of
NEMA Type 10-50R.
4-wire receptacle
3-wire receptacle (10-50R)