Electrical Requirements

Observe all governing codes and ordinances. 

Ensure that the electrical installation is adequate and in 
conformance with National Electrical Code, ANSI/NFPA 70 (latest 
edition), or CSA Standards C22.1-94, Canadian Electrical Code, 
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes 
and ordinances.

If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrician determine that the 
ground path is adequate.

A copy of the above code standards can be obtained from:

National Fire Protection Association

One Batterymarch Park

Quincy, MA 02269

CSA International

8501 East Pleasant Valley Road

Cleveland, OH 44131-5575

A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is 
required.

If the house has aluminum wiring, follow the procedure 
below:

1. Connect a section of solid copper wire to the pigtail 

leads.

2. Connect the aluminum wiring to the added section of 

copper wire using special connectors and/or tools 
designed and UL listed for joining copper to aluminum.

Follow the electrical connector manufacturer's recommended 
procedure. Aluminum/copper connection must conform with 
local codes and industry accepted wiring practices.

Wire sizes and connections must conform with the rating of 
the appliance as specified on the model/serial rating plate. 
The model/serial plate is located behind the filter on the rear 
wall of the range hood.

Wire sizes must conform to the requirements of the National 
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA 
Standards C22. 1-94, Canadian Electrical Code, Part 1 and 
C22.2 No. 0-M91 (latest edition) and all local codes and 
ordinances.

INSTALLATION INSTRUCTIONS

Prepare Location

It is recommended that the vent system be installed before 
the range hood is installed.

Before making cutouts, make sure there is proper clearance 
within the ceiling for exhaust vent.

Range hood is to be installed 24" (61.0 cm) min. for electric 
cooking surfaces, 27" (68.6 cm) min. for gas cooking surfaces, 
to a suggested maximum of 36" (91.4 cm) above the cooking 
surface.

Check your ceiling height and the range hood height 
maximum before you select your hood.

1. Disconnect power.

2. Determine which venting method to use: roof, wall or non-

vented.

3. Select a flat surface for assembling the range hood. Place 

covering over that surface.

4. Using 2 or more people, lift range hood onto covered surface.

5. Determine and mark the centerline on the ceiling where the 

range hood will be installed, considering the requirements for 
ceiling support structures. See the “Location Requirements” 
section. Make sure the range hood is centered over the 
cooking surface.

6. Tape template in place on the ceiling at the marked 

centerline.

7. Use a pencil to mark the mounting screws, wire access and 

duct hole locations on the ceiling.

NOTE: Mounting hole locations should be into the ceiling 
support structure.

Remove the template.

8. Drill 4 - 

³⁄₁₆

" (4.8 mm) pilot holes for mounting the upper 

horizontal support. 

9. Determine the required location for the home power supply 

cable and drill a ½" (1.3 cm) diameter hole for wire access.

10. Run wire through the home power supply cable according to 

the National Electrical Code or CSA Standards and local 
codes and ordinances. There must be enough ½" conduit 
and wires from the fused disconnect (or circuit breaker) box 
to make the connection in the hood’s electrical terminal box.

NOTE: Do not reconnect power until installation is complete.

Use caulk to seal all openings.

11. (For vented installations only.) Using a jigsaw or keyhole saw, 

cut a 8½" (21.6 cm) diameter hole for the vent duct.

WARNING

Excessive Weight Hazard

Use two or more people to move and install 
range hood.

Failure to do so can result in back or other injury.

Содержание 36'' ISLAND-MOUNT CANOPY RANGE HOOD

Страница 1: ...6247 or visit our website at www jennair com In Canada call 1 800 807 6777 or visit our website at www jennair ca Instructionsd installationetGuided utilisationetd entretien Au Canada pour assistance...

Страница 2: ...Installation des filtres 23 Achever l installation 23 UTILISATION DE LA HOTTE 23 Afficheur 23 clairage 24 Minuterie 24 Boutons de vitesse du ventilateur 24 ENTRETIEN DE LA HOTTE DE CUISINI RE 25 Nett...

Страница 3: ...e American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities When cutting or drilling into wall or ceiling do not damage electrical wiring and othe...

Страница 4: ...ructure behind the plaster or drywall The support structure must be able to support 80 lbs 36 6 kg The range hood is factory set for venting through the roof or wall For non vented recirculating Insta...

Страница 5: ...ide of the thermal break The break should be as close as possible to where the vent system enters the heated portion of the house Makeup Air Local building codes may require the use of makeup air syst...

Страница 6: ...ge hood is installed Before making cutouts make sure there is proper clearance within the ceiling for exhaust vent Range hood is to be installed 24 61 0 cm min for electric cooking surfaces 27 68 6 cm...

Страница 7: ...x 8 mm screws and tighten Connect Vent System 1 Install vent system 2 Push duct over the exhaust outlet Seal all connections with vent clamps Non Vented recirculating Installation 1 Attach the air de...

Страница 8: ...er 10 Check all light bulbs are secure in their sockets 11 Reconnect power InstallDuctCovers 1 Attach the vertical duct cover supports using 4 4 x 8 mm screws 2 Slide upper duct covers into place unti...

Страница 9: ...r saturation alarm press and hold the POWER INCREASE button for 5 seconds The Clean Grease Filter icon will no longer be displayed Charcoal Filter Saturation Alarm After 120 hours of fan function the...

Страница 10: ...ng 5 seconds after selecting the desired time will start the timer countdown 3 The timer can be canceled at any time by pressing the Timer button again NOTE During the timer setup the Power Decrease a...

Страница 11: ...he highest temperature setting To reactivate the filter the filter should be dried in an oven for 10 minutes with a maximum temperature of 210 F 100 C To Replace Charcoal Filters 1 Turn fan and lights...

Страница 12: ...Power Board Electronic User Interface 1 2 3 4 5 1 2 3 4 5 6 W R GY BR Y BR Y G BR BR R R BK BR R BR Transformer PRI Y Y SEC Y Y Transformer I R P Y Y C E S M GY W R BK BU BU R W GY BK 1 Y G G Y BU W B...

Страница 13: ...name address and daytime telephone number 2 Appliance model number and serial number 3 Name and address of your dealer or servicer 4 A clear description of the problem you are having 5 Proof of purcha...

Страница 14: ...e service by an authorized Jenn Air servicer is not available 10 The removal and reinstallation of your major appliance if it is installed in an inaccessible location or is not installed in accordance...

Страница 15: ...n cas de non respect des instructions Votre s curit et celle des autres est tr s importante Nous donnons de nombreux messages de s curit importants dans ce manuel et sur votre appareil m nager Assurez...

Страница 16: ...que d incendie et vacuer ad quatement les gaz veiller acheminer l air aspir par un conduit jusqu l ext rieur ne pas d charger l air aspir dans un espace vide du b timent comme une cavit murale un plaf...

Страница 17: ...i C est l installateur qu incombe la responsabilit de respecter les distances de s paration sp cifi es sur la plaque signal tique de l appareil La plaque signal tique de l appareil est situ e derri re...

Страница 18: ...m pour des performances optimales Pour un fonctionnement efficace et silencieux Ne pas utiliser plus de trois coudes 90 Veiller ce qu il y ait une section droite de conduit d un minimum de 24 61 0 cm...

Страница 19: ...de liaison la terre il est recommand qu un lectricien qualifi v rifie la qualit de la liaison la terre Pour obtenir un exemplaire de la norme des codes ci dessus contacter National Fire Protection As...

Страница 20: ...QUE Les trous de montage devront tre perc s dans la structure de soutien du plafond Retirer le gabarit 8 Percer 4 avant trous de 4 8 mm pour le montage du support horizontal sup rieur 9 D terminer l e...

Страница 21: ...ions Installation sans d charge l ext rieur recyclage 1 Fixer le d flecteur d air au support horizontal sup rieur l aide des 4 vis de montage 2 Mesurer la longueur de conduit d vacuation de 8 20 3 cm...

Страница 22: ...de connexion 10 Inspecter chaque lampe v rifier que chaque lampe est bien ins r e dans sa douille 11 Reconnecter la source de courant lectrique Installationdescache conduits 1 Fixer les supports de ca...

Страница 23: ...de commande Les commandes de la hotte sont situ es l avant de la hotte Afficheur Alarme de saturation du filtre graisse Apr s 30 heures de fonctionnement du ventilateur l affichage indique Clean Grea...

Страница 24: ...ventilateur retourne au r glage qui avait t effectu avant que le niveau de chaleur excessif ne soit d tect clairage Fonctionnement de l clairage 1 Appuyer sur le bouton de symbole d clairage pour met...

Страница 25: ...ns horaire pour le verrouiller en place Filtres charbon Installation sans d charge l ext rieur recyclage REMARQUE On doit remplacer le filtre charbon apr s environ 3 ans d utilisation Pour commander u...

Страница 26: ...ilisateur lectronique 1 2 3 4 5 1 2 3 4 5 6 BL R GRIS MAR JA MAR JA VE MAR MAR R R N MAR R MAR Transformateur PRI JA JA SEC JA JA Transformateur I R P JA JA C E S M GRIS BL R N BU BU R BL GRIS N 1 VE...

Страница 27: ...ez vous de conserver la preuve d achat pour v rifier les conditions de la garantie Si le marchand ou la compagnie de service ne peut pas r soudre votre probl me crivez Jenn Air Brand Home Appliances C...

Страница 28: ...ou n est pas install conform ment aux instructions d installation fournies 11 Les gros appareils m nagers dont les num ros de s rie et de mod le originaux ont t enlev s modifi s ou qui ne peuvent pas...

Отзывы: