12
Please consult your manual for full information or consult your local dealer.
Item
Function
G
Silence Horn
Turns off an alarm horn (if configured) and enters the alarm menu.
H
Shortcut Menu
Gives access to: Jump menu, mode selection, test and lamp test .
J
Semi-Auto Mode
The controller cannot automatically start, stop, connect or disconnect the generator.
The operator can start, stop, connect or disconnect the generator.
The controller automatically synchronises before closing a breaker, and
automatically de-loads before opening a breaker.
K
Mains Symbol
Green: The mains voltage and frequency are ok, and the controller can
synchronise and close the breaker.
Red: Mains failure.
L
Close Breaker
Press to close the breaker.
M
Open Breaker
Press to open the breaker.
N
Breaker Symbols
Green: Breaker is On.
Green flashing: Synchronising or de-loading.
Red: Breaker failure.
P
Generator
Green: The generator voltage and frequency are OK, and the controller can
synchronise and close the breaker.
Green flashing: The generator voltage and frequency are OK, but the Voltage
and Hertz OK timer is still running. The controller cannot close the breaker.
Red: The generator voltage is too low to measure.
Q
Engine
Green: There is running feedback.
Green flashing: The engine is getting ready.
Red: The engine is not running or there is no running feedback.
R
Stop
Stops the generator if semi-auto or manual is selected.
S
Start
Starts the generator if semi-auto or manual is selected.
T
Load Symbol
Off: Power management application.
Green: The supply voltage and frequency are OK.
Red: Supply voltage/frequency failure.
Control panel – DEIF AGC 150