9. Heat Control with Outdoor Temperature Control 

PW control automatically adjusts the 
temperature of heating system water. Need of 
heat varies according to outdoor temperature. 

Heating system water temperature is 
controlled via the heating curve. The colder 
outdoor temperature is, the warmer the 
heating system water is adjusted. Low-pitched 
curve (22-25) is typically suitable for houses 
with underfloor heating system, for which 
over 40°C temperature cannot be used. For 
example: If the selected curve is 25, heating 
system water temperature is approx. 25°C, 
when outdoor temperature is 0 °C. 

The curve can be steeper in houses with 
radiator heating system. Recommended 
starting curve is 35. With this curve heating 

system water temperature is approx. 35°c, 
when outdoor temperature is 0 °C. In less 
energy-efficient houses even steeper curves 
can be used. 

If room temperature decreases when outdoor 
temperature drops, select steeper curve 
(bigger number) and vice versa. If room 
temperature is constantly either too cold or 
too warm, adjust temperature in x °C 
or decrease - x °C in fine adjustment board. 

If PW is introduced at the construction stage 
of the property and the floors are still drying 
up, we recommend using low temperatures 
for heating system. Select lowest curve (22) 
and set fine adjustment for temperature at       
-20°C - -15°C.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Picture 3. Heating curve 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание PW

Страница 1: ...ELECTRIC BOILER PW INSTALLATION AND OPERATION MANUAL J SPI KNOWS HOW TO CREATE WARMTH AND COMFORT JASPI UK www northmangroup co uk Telephone 01392 247340 Email info northmangroup co uk...

Страница 2: ...ture Decrease 9 5 Maintenance Menu 10 Troubleshooting 10 1 Insufficient Heat 10 2 Empty Automatic Control Screen 10 3 If the Cause of the Trouble Is Not Found 10 4 Resistance Values of Boiler Sensors...

Страница 3: ...eating water temperatures maintains suitable user defined temperature in the heating system The boiler also functions without outdoor temperature control with a so called set temperature control PW is...

Страница 4: ...3 1 Function Diagram...

Страница 5: ...12 l Circulation pump 180 mm 25 40 R3 4 Safety relief valve DN 15 1 5 bar Automatic deaeration Shutoff drain R1 2 Max temperature 100 C Min temperature 0 C Supply Outdoor temperature sensor 1 current...

Страница 6: ...olation 6 Water level switch 7 Circulation pump 8 Pressure gauge 9 Wall bracket 10 Sensor probe 11 Safety valve pipe R20 12 Drain and filling valve R15 13 Return Inlet R20 14 Outlet R20 15 Electric le...

Страница 7: ...of the boiler back side and detach the bracket 2 Mount the bracket to a reinforced wall with four screws 3 Hang the boiler on the bracket hooks 4 Attach the two screws pulled out on phase 1 on top of...

Страница 8: ...e equipped with a valve BY PASS valve which ensures the circulation between pump and boiler 6 Electric Wiring Only an authorized and qualified wiring company can install electric wiring Unit s interna...

Страница 9: ...re that melt water and icing will not cause damage to the sensor If the outdoor sensor is installed near the wall inlet make sure that the inlet is insulated properly 10 11 Connection of current trans...

Страница 10: ...7 Electrical Diagram...

Страница 11: ...tches and automatic controls Check the safety relief valves of the heating unit at least twice a year The safety valve is activated by turning it anti clockwise and water flows through the safety valv...

Страница 12: ...ature is 0 C The curve can be steeper in houses with radiator heating system Recommended starting curve is 35 With this curve heating system water temperature is approx 35 c when outdoor temperature i...

Страница 13: ...9 1 Front Panel...

Страница 14: ...control unit screens Normally the screen visible is basic screen state but when the timer is set or the unit receives power limitation or trouble messages the screen varies between basic screen state...

Страница 15: ...9 3 Settings Heating control basic settings heating curve selecting fine adjusting and temperature limits...

Страница 16: ...9 4 Temperature Decrease This screen state is for selecting if a lower or higher heating setting is being used at a certain time of day...

Страница 17: ...9 5 Maintenance Menu For the installer only The service menu is for setting main fuse size of the property and max power of the unit...

Страница 18: ...oor boiler sensor troubles the Error NOT CONNECTED message will be displayed on the screen When the outdoor sensor fails the automatic system will assume the outdoor temperature to be 0 C When the boi...

Страница 19: ...set temperature according to set value 10 80 C When the boiler sensor is removed the regulator will switch power off 10 5 Current Transformer Check Current values applied to the main fuses of the hous...

Страница 20: ...ower of the boiler stage limitation 1 6 See table at section 6 and 6 3 kW Step 6 12 2 kW Set value corresponding to the main fuse of the house 16 70 A A 63 A Temperature decrease 0 20 C C 0 C Selected...

Отзывы: