Compressor heater
JÄSPI Inverter Nordic is equipped with two compressor
heaters that heat the compressor before start-up and
when the compressor is cold.
The compressor heater (EB10) must have been active for
at least 3 hours before compressor operation can be
initiated. This is done by connecting control voltage.
JÄSPI Inverter Nordic permits compressor start after the
compressor has been warmed up. This can take up to 3
hours.
NOTE
The compressor heater must have been active
for approx. 3 hours before the first start, see
section “Start-up and inspection”.
Condensation
The condensate drain pan collects and leads away the
condensation water.
NOTE
It is important to the heat pump function that
condensation water is led away and that the
drain for the condensation water run off is not
positioned so that it can cause damage to the
house.
Condensation run-off should be checked regu-
larly, especially during the autumn. Clean if
necessary.
■
The condensation water (up to 50 litres/24 hrs) that
collects in the trough should be routed away by a pipe
to an appropriate drain, it is recommended that the
shortest outdoor stretch possible is used.
■
The section of the pipe that can be affected by frost
must be heated by the heating cable to prevent
freezing.
TIP
Pipe with heating cable for draining the
condensation water trough is not included.
To ensure the function, the accessory KVR 11
should be used.
■
Route the pipe downward from the heat pump.
■
The outlet of the condensation water pipe must be at
a depth that is frost free or alternatively indoors (with
reservation for local ordinances and regulations).
■
Use a water trap for installations where air circulation
may occur in the condensation water pipe.
■
The insulation must seal against the bottom of the
condensation water trough.
Drainage of condensation
Stone caisson
LEK
Frostfritt djup
F2120
Frost proof
depth
If the house has a cellar the stone caisson must be posi-
tioned so that condensation water does not affect the
house. Otherwise the stone caisson can be positioned
directly under the heat pump.
Drain indoors
Water seal
The condensation water is lead to an indoor drain (sub-
ject to local rules and regulations).
When routing pipes indoors, condensation water pipes
must be insulated against condensation.
Route the pipe downward from the heat pump.
The condensation water pipe must have a water seal to
prevent air circulation in the pipe.