background image

 
 

 
 
 
 

 

INSTALLATION AND OPERATION MANUAL 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

HIGH EFFICIENCY 

SOLID FUEL BOILER 

JASPI – HEATING PROFESSIONAL 

WWW.JASPI.UK

Содержание Econature 40

Страница 1: ...INSTALLATION AND OPERATION MANUAL HIGH EFFICIENCY SOLID FUEL BOILER JASPI HEATING PROFESSIONAL WWW JASPI UK...

Страница 2: ...am 7 Boiler Operation and Maintenance 8 Fuel 8 Start up 8 Control Panel 9 Firewood burning 10 Combustion Air Control 11 Maintenance 12 Cleaning 13 Troubleshooting 13 The boiler water temperature does...

Страница 3: ...ns at a temperature above 100 C when the temperature exceeds 280 C the resulting reaction causes heat re lease Secondary combustion the reaction between pyrolytic gases and oxygen begins at a temperat...

Страница 4: ...e 110 C Min temperature 0 C Max pressure 3 0 bar Standard pressure 1 5 bar Power consumption 0 12 kW Voltage 230 V Frequency 50 Hz Body protection IP 2X Furnace dimensions height 600 mm width 350 mm a...

Страница 5: ...accumulator 10 R15 FH drain connection 11 R25 FH expansion connection 12 R15 FH flue gas sensor analyzer connec tion 13 Sensor panel 14 Flame monitor glass 15 Upper primary air adjusting damper 16 Low...

Страница 6: ...rs into the battery bottom middle and top The system should be fitted with shutoff val ves in order to ensure easy filling and empty ing of the boiler accumulator and heating system The boiler should...

Страница 7: ...32 72 C charging pack 6 OVALI 1800 energy accumulator 7 J SPI tubular electric heater max 5 ea 8 Heating loop pump 9 Accumulator thermometer 3 ea 10 Boiler water filling valve 11 Pump thermostat Power...

Страница 8: ...woods cause more contamination to the boi ler Different woods burn differently Lighter woods with a smaller wood diameter will burn better Start up Check that The flue is open and there is no install...

Страница 9: ...tes the smoke exhauster when the flue gas temperature drops to the setpoint 6 Power switch The power switch of the smoke exhauster and the charging pump 7 Pump thermostat indicator lamp On when the pu...

Страница 10: ...ard onto the bar so that the blocks touch the rear wall of the furnace Set the smoke exhauster thermostat to the setpoint which is about 90 C The set point is correct if the smoke exhauster stops when...

Страница 11: ...and ratio for burning varies depending on the wood to be burnt Primary and secondary air is factory adjusted for birch firewood Upper primary air does not have to be ad justed under normal operating c...

Страница 12: ...ains air oxygen The hot system pressure should be lower than 1 5 bar and the cold system pressure higher than 0 5 bar 1 5 bar safety relief The water volume varies as the tempera ture i e the higher t...

Страница 13: ...boiler water temperature does not rise to the desired level Ensure that the primary and secondary air ratio and access are correct Ensure that the firewood is dry If there is a cooling coil in the bo...

Страница 14: ...that the thermostat indi cator lamp is on since the set value of the extractor thermostat is 90 C Check the set value of the flue gas ther mostat Check that the temperature limiter has not tripped For...

Страница 15: ...170 C Reduced flue pressure Pump speed Pump speed Upper primary air 0 Lower primary air 0 Secondary air 0 Expansion tank pre pressure Signature Warranty The warranty is confirmed to be two years for t...

Страница 16: ...ncy Declared agency 0424 Inspecta EY inspection certificate for the development of RS 419 07 Testing has been conducted to EN 303 5 test agency SP Sveriges Tekniska Forskningsinstitut declared agency...

Отзывы: