Revision 1: May 2018 Jarvis Lighting
’
s Terms and Conditions are available at www.jarvislighting.com
AL-EMER
S
ERIES
–
O
PERATION
I
NSTRUCTIONS
Normal Mode - AC Power Present
The AC driver operates the LED load
as designed. The emergency pack is
charging in a standby mode. The test
button will be lit, indicating the
presence of AC power.
Standby power consumption: 3.7W
Emergency Mode - Power Failure
In the event of a power failure, the
LED emergency driver switches to
emergency mode and operates
alternate LEDs for a minimum of 90
minutes.
AL-EMER
S
ERIES
–
M
AINTENANCE
I
NSTRUCTIONS
NFPA 101, Life Safety Code outlines the following schedule:
Monthly - Ensure that the test button light is illuminated. Conduct a 30 second discharge test by depressing the test
button. The LED load should operate at reduced output (as it would in Emergency Mode).
Annually - Ensure that the test button is illuminated. Conduct a full 90 minute discharge test. The unit should operate as
intended for the duration of the test.
"Written records of the testing shall be kept by the owner for inspection by the authority having jurisdiction."
Testing procedures are as follows:
30 Second Discharge Test
Press the test button to cut the power to the AC driver and switch the system to Emergency Mode. Release the test button
to return to Normal Mode.
90 Minute Discharge Test
Switch off the circuit breaker to simulate a full power outage.
Initial Testing
Allow the unit to charge approximately one hour, then conduct a short discharge test. Allow a 24 hour charge before
conducting a one hour test.
Servicing to be performed by qualified service personnel only!