17
Digital inputs
The UMG 510 has 8 digital inputs arranged in two
groups of 4 inputs each.
Each group of inputs has its own common ground
terminal and is insulated to the internal circuits as
well as to the other group of inputs. Active inputs re-
quire an input voltage of 10..28V at max. current of
6mA.
Fig. Connection diagram of 2 external relays to the
digital outputs.
Digital I/O
Digital outputs
The UMG 510 has 5 digital outputs. The outputs are
insulated from the internal electronics. The output
transistors are arranged as high side switches with
common plus terminal (terminal no. 11). Each tran-
sistor can drive 30mA and withstands max. 28V
open circuit voltage.
Fig. Connection diagram of 2 external contacts to
digital inputs 3 and 4.
+24V=
11
12
13
14
15
16
Digital
Output 5
Digital
Output 4
Digital
Output 3
Digital
Output 2
Digital
Output 1
UMG510
Digital outputs
K1
K2
+
-
230V AC
24V DC
Externe
Hilfsspannung
3,9V
4k
7
6
Digital
Input 4
3,9V
4k
8
Digital
Input 3
3,9V
4k
9
Digital
Input 2
3,9V
4k
10
Digital
Input 1
UMG510
Digital inputs1-4
24V
DC
+
-
S1
S2
Installation
Содержание UMG510
Страница 39: ...39 Technical data...
Страница 40: ...40 Dimension sketch Cut out 138 0 8 x 138 0 8 mm Back view Patchkabel Technical data...