19
English
Address Meaning
Setting range Pre-setting
080
M-Bus primary address (UMG96S)
0 .. 250
1
081
M-Bus baud rate
1)
0
..
7
5
082
Number of data points for RSP_UD2
0 .. 39
0
2)
083
As an extension secondary addr., Part 1 0 .. 99
3)
084
As an extension secondary addr., Part 2 0 .. 99
3)
085
As an extension secondary addr., Part 3 0 .. 99
3)
086
As an extension secondary addr., Part 4 0 .. 99
3)
1)
0 = 300, 1 = 600, 2 = 1200, 3 = 2400, 4 = 4800, 5 = 9600, 6 = 19200, 7 = 38400 baud
2)
0 = All data points. In order to call up all data points, two telegrams must be sent.
3)
The extended secondary address is preset by the manufacturer with the device
serial number.
Baud rate
The UMG96S can be operated on the M-bus interface with the following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200 and 38400 baud.
The baud rate can be changed over the M-Bus.
Number of data points
Here you stipulate how many data points should be transmitted. Individual data
points cannot be selected.
Example: Reading out the data points 1 to 6.
Enter a 6 into the UMG96S on address 82.
All data points, up to and including data point 6, are transmitted with every request.
Example: You require only the data point 10.
Enter a 10 into the UMG96S on address 82.
All data points, up to and including data point 10, are transmitted with every request.
Use only the data point 10 required and ignore the received but not required data
points.