UMG 96RM-P/-CBM
Connection capacity of the terminals (voltage and current measurement)
Connectable conductor. Only one conductor may be connected per contact point!
Current
Voltage
Single-wire, multi-wire, finely stranded conductor
0.2 - 2.5mm
2
, AWG 26-12
0.08 - 4.0mm
2
, AWG 28-12
Pin terminals, ferrules
0.2 - 2.5mm
2
0.2 - 2.5mm
2
Tightening torque
0.4 - 0.5Nm
0.4 - 0.5Nm
Stripping length
7mm
7mm
Current measurement I1 - I4
Rated current
5A
Measurement range
0 .. 6A
rms
Crest factor
1.98
Resolution
0.1mA (Display 0.01A)
Overvoltage category
300V CAT II
Measurement surge voltage
2kV
Power consumption
ca. 0.2 VA (Ri=5mOhm)
Overload for 1 sec.
120A (sinusoidal)
Sampling frequency
21.33kHz (50Hz), 25.6 kHz (60Hz) per measurement channel