51
UMG 806
www.janitza.com
10.2.7 Configuring the RS-485 interface (Mod-
bus)
To operate the device via the RS-485 interface (see
chapter „7.8 RS-485 interface“ on page 38),
configure the following parameter addresses:
·Device address
·Baud rate
·Parity
·Operating mode
Address
Designation
200
Device address (1 .. 247)
201
Baud rate, RS-485
0 = 9,600 bit/s
1 = 19,200 bit/s
2 = 38,400 bit/s
3 = 57,600 bit/s
4 = 115,200 bit/s
202
RS-485, parity
0 = N.8.1
1 = E.8.1
2 = O.8.1
3 = N.8.2
203
RS-485, mode
0 = Modbus RTU/slave
1 = Modbus RTU/master
Tab.: Configuration of the RS-485 interface
Configure the parameters above as already de-
scribed in section „10.2 Configuration“ on page
47.
INFORMATION
A parameter list can be found in chapter „10.3
10.2.8 Configuring the Ethernet interface
INFORMATION
The description of the Ethernet interface (mod-
ule 806-EC1) can be found in chapter „13.7.2
Содержание UMG 806
Страница 9: ...9 UMG 806 www janitza com...
Страница 21: ...21 UMG 806 www janitza com...
Страница 24: ...24 UMG 806 www janitza com 4 2 Front view side view 90 mm 3 54 in 90 mm 3 54 in 63 5 mm 2 5 in 35 mm 1 38 in...
Страница 55: ...55 UMG 806 www janitza com...
Страница 62: ...62 UMG 806 www janitza com 13 3 Front side views 13 3 1 806 EC1 module 13 3 2 806 ED1 module...
Страница 81: ...81 UMG 806 www janitza com...
Страница 85: ...85 UMG 806 www janitza com...