32
Voltage measurement
The voltage measurement inputs are suitable for measurements in the following
power supply systems
Three-phase 4-conductor systems with
nominal voltages up to
480 VAC
Three-phase 3-conductor systems,
unearthed, with nominal voltages up to
277 VAC
From a safety and reliability perspective, the voltage measurement inputs
are designed as follows
Overvoltage category
230V: CAT II
24 V: CAT III
Protection of voltage measurement
Impedance limited plus clamping diodes
/ MOV
Measurement range L-N
0 .. 277 VAC
Measurement range L-L
0 .. 480 VAC
Resolution
0.01 VAC
Crest factor
1.9 @ 240 VAC
Impedance
2.5 MΩ
Power consumption
<0.1 A @ 277 VAC (< 3 W)
Sampling rate
40 kHz
Frequency range of the fundamental oscillation
40 .. 70 Hz
Digital inputs
Quantity
2
Note:
two inputs for dry contacts