UMG 605US
Current measurement connection
options
The UMG605US recognises two connection
options for the current measurement.
Connection option 0
•
Measurement via 3 current transformers
in three-phase 4-conductor systems.
•
Measurement via 2 current transformers
in systems with the same load.
Connection option 1
•
Measurement via 2 current transformers
(Aron circuit) in three-phase 3-conductor
systems.
Address Connection option
110
0 = Three current transformers.
(Default factory setting)
1 = Two current transformers
(Aron circuit)
Fig. 49.1 Section of the parameter list for the
current transformer connection options.