61
UMG 604
Possible error
Active power
too
small or too large.
No connection
with
the device.
Despite the meas-
ures above the device
does not work.
Cause
The programmed current
transformer transformation
ratio is incorrect.
The current path is assigned
to the wrong voltage path.
The programmed voltage
transformer transformation
ratio is incorrect.
RS485:
- Device address is incorrect.
- Wrong protocol.
- Termination missing.
Ethernet:
- IP address incorrect
- The concealed key
(service) was used.
Device is defective.
Remedy
Read out and program the current
transformer transformation ratio at the
current transformer.
Check connection and correct if
necessary.
Read out and program the voltage
transformer transformation ratio at the
voltage transformer.
Adjust the device address.
Select protocol.
Close bus with terminating resistor
(120 ohm).
Adjust IP address at the device.
Overwriting the address 204 with 0 and
set IP address or select DHCP/Zeroconf
(address 205).
Send device to the manufacturer for
checking with a precise description of
the error.
Содержание UMG 604
Страница 29: ...29 UMG 604 ...
Страница 47: ...47 UMG 604 ...
Страница 78: ...78 UMG 604 Dimensioned drawings Front view Side view ...