Page 6

Universal Measuring Device UMG 500A

"opt.": optional; see Special versions
"sqrt": square root
"Ref.": reference conditions for the accuracy data:

frequency

49.5 .. 50.5Hz or 59.5 .. 60.5Hz

harmonic content

<10% of basic wave

ambient temperature

+18°C ... +27°C

current and voltage

in the range 20% ... 90% of measuring range

cos phi

in the range 0.5 ind -1 - 0.5 cap

Functional plan

Mea-

sured

values

Measurement

function

Voltage

U

App.

current I

Mean

current

Mean

real

power

Real

power P

App.

power S

React.

power Q

React.

work

Real

work W

Fre-

quency f

power

factor

cos phi

5.

7. 11. 13.

Harmonic wave

Measuring method

Ueff

Ieff

15 min./

99.5%

W /

Restzeit

measure

P

S = Ueff*

Ieff

Q =

sqrt

(S²-P²)

Q*t

W = P*t

zero

crossing

P/S

Fourier analysis

Summation 4-wire

measurement

-

-

-

P1+P2

+P3

P1+P2

+P3

S1+S2

+S3

Q1+Q2

+Q3

(Q1+Q2

+Q3)*t

(P1+P2

+P3)*t

-

Sum (P)

----------

Sum (S)

-

-

-

-

Summation 3-wire

measurement (option)

-

-

-

P1+P3

P1+P3

(S1+S2

+S3)

/sqrt (3)

Q1+Q3

(Q1+

Q3)*t

(P1+

P3)*t

-

-

-

-

-

Dis-
play

func-
tions

Sign

ind / cap

-

-

-

-

-

-

x / x

x / -

-

-

x / x

-

-

-

-

Motor/
gener.

-

-

-

x / -

x / x

-

-

-

x / -

-

x / x

-

-

-

-

Transient

values

L1

0 .. 9999

V / opt.:

0.00 ..

99.99 kV

0 .. 5500

A

0 .. 5500

A

-

0 .. 9999

kW / opt.:

0.00 ..

99.99

MW

0 .. 9999

kVA /

opt.: 0.00

.. 99.99

MVA

0 .. 9999

kvar

0.000 ..

9999

kvarh

(*255)

0.000 ..

9999

kWh

(*255)

48.00 ..

62.00Hz

100

0.0 .. 25.5%

L2

-

-

L3

-

-

Sum

-

-

-

0 .. 9999

kW

-

-

-

-

-

Peak values

L1

0 .. 9999

V / opt.:

0.00 ..

99.99 kV

0 .. 5500

A

0 .. 5500

A

-

-

-

48.00 ..

62.00Hz

0.0 .. 25.5%

L2

-

-

-

-

L3

-

-

-

-

Sum

-

-

-

0 .. 9999

kW

-

-

-

-

-

-

-

Date/
Time

x

x

x

x

x

x

x

-

-

x

x

-

-

-

-

Accuracy referred to full scale

value

+/- 2

digit

+/- 2

digit

+/- 2

digit

+/- 5

digit

+/- 5

digit

+/- 5

digit

+/- 5

digit

+/- 5

digit

+/- 5

digit

+/- 2

digit

+/- 2

digit

+/- 10 digit

+/- 0.5 % +/- 0.5 % +/- 0.5 % +/- 1.5 % +/- 1.0 % +/- 1.0 % +/- 1.5 % +/- 1.5 % +/- 1.0 % +/- 0,5 % +/- 1.0 %

+/- 10 %

Scaling of analogue output

0..20 mA / optionally 4..20 mA

(resolution 8 bit)

0 .. 9999

V / opt.:

0.00 ..

99.99 kV

0 .. 9999

A

0 .. 9999

A

0 .. 9999

kW

0 .. 9999

kW / opt.:

0.00 ..

99.99

MW

0 .. 9999

kVA /

opt.: 0.00

.. 99.99

MVA

9999 ind.

.. 0 ..
9999

cap.

0=10mA

0 .. 9999

varh /

pulse

(see

"scaling

of ana-

logue

output")

0 .. 9999

Wh /

pulse

(see

"scaling

of ana-

logue

output")

Variation

from

50/60 Hz

in 0.01

Hz steps

50/60 Hz

=10 mA

Variation

from 1.00

in 0.01

steps

1=10mA

0 .. 25%

Setting range of threshold

contacts

0 .. 9999

V / opt.:

0.00 ..

99.99 kV

0 .. 9999

A

0 .. 9999

A

0 .. 9999

kW

0 .. 9999

kW / opt.:

0.00 ..

99.99

MW

0 .. 9999

kVA /

opt.: 0.00

.. 99.99

MVA

9999 ind

.. 0 ..

9999cap

0 .. 9999

kvarh

(without

over-

flows)

0 .. 9999

kWh

(without

over-

flows)

00.00 ..

99.00Hz

0.00ind

...

1.00

...

0.00capp

0 .. 25%

rem.time

Содержание UMG 500 A

Страница 1: ...Universal Measuring Device UMG 500 A Janitza electronic GmbH Vor dem Polst ck 1 D 35633 Lahnau Tel 0 64 41 9642 0 Fax 0 64 41 9642 30 Doc No 1 010 006 1...

Страница 2: ...9 Real power 9 Mean real power 9 Measuring period 9 Remaining time 9 Reactive power 10 Real work 10 Reactive work 10 Frequency 10 Power factor 10 Harmonic wave content of voltage 10 Analogue output 1...

Страница 3: ...analogue output threshold contacts serial interface designed for networking Application 1 Peak values of harmonics are stored without date and time Construction features Universal Measuring Device UM...

Страница 4: ...1 to 3 or 4 to 6 If the reading falls below the min value programmed for the threshold function or rises above the max value the appropriate relay is activated The threshold values min and max can be...

Страница 5: ...onnect current path for L1 4 1 1 Switch on auxiliary voltage measured voltage and measured current 4 1 2 Using the operating keys of the UMG 500A cause the current in L1 to be displayed and compare it...

Страница 6: ...99 kV 0 5500 A 0 5500 A 0 9999 kW opt 0 00 99 99 MW 0 9999 kVA opt 0 00 99 99 MVA 0 9999 kvar 0 000 9999 kvarh 255 0 000 9999 kWh 255 48 00 62 00Hz 100 0 0 25 5 L2 L3 Sum 0 9999 kW Peak values L1 0 9...

Страница 7: ...by trained staff after a period of about 5 years The batteries have a design life of approx 8 to 10 years Batteries 2 off Lithium batteries voltage 3 V diameter 12 5 mm 2 5 mm thick Panasonic order c...

Страница 8: ...measurement function Erasing the accumulated work Restart of averaging power and current Summe sum Selection key sum With this key the sums of the measurement functions real power apparent power reac...

Страница 9: ...y service therealpowerisdisplayedwiththreedigitsas Asanoption theinstrumentcandisplaytherealpower in MW to two decimal places P U I Apparent power This function shows the apparent power of the measure...

Страница 10: ...ly after erasure If there is a power failure the time measurement will be interrupted Frequency This function displays the frequency of the voltage in L1 The unit of measurement is indicated by the LE...

Страница 11: ...al to or bigger than 500 if the maximum pulse frequency of 0 25 Hz should not be exceeded 0 20mA Analogue output Allocation In order to allocate a particular measuring function to the output the desir...

Страница 12: ...bed under Peak values but using key 5A instead of the function key for the corresponding measurement value In combination with the keys and the settings can be changed There is no automatic changeover...

Страница 13: ...at care must be taken to ensure that the parallel port of the PC 25 pin socket is not used because otherwise damage to the device can occur Alternatively a connecting cable 25 pin socket socket can be...

Страница 14: ...ng stations using the master slave principle i e the measuring stations never transmit independently only after being called up by the host system The protocol consists essentially of control characte...

Страница 15: ...digit kW kVA cos phi kWh 1 5 digit kvar kvarh 1 5 5 digit Harmonic wave content 10 10 digit Environment Operating temperature 10 C 45 C Storage temperature 20 C 60 C Humidity class F to DIN 40040 15...

Страница 16: ...ion switch closed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts auxiliary voltage see nameplate consumer measured voltage see nameplate interface c...

Страница 17: ...4 wire switch closed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts interface converter RS 485 RS 232 switch closed remote switch open local consume...

Страница 18: ...osed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts interface converter RS 485 RS 232 switch closed remote switch open local auxiliary voltage see n...

Страница 19: ...ive ground terminal and is suited for applications in overvoltage category III and contamination level 2 EN 55011 06 1992 RFI product standard Group 1 Class B residential and commercial premises EN 50...

Отзывы: