Schematic diagram: MRG 96RM-E Flex design
Settings, parametrisation and safety information apply in accordance with the
installation and operating instructions enclosed.
m
MRG 96RM-E Flex RCM
PE
N
L1
Spannungsmessung 1-4
Voltage Input 1-4
L2
Strommessung 1-4
Current Input 1-4
I
1
L3
Verbraucher
Loads
I
PE
I
DIFF
0-30
mA
RCM
Ether
net
10/100Base-T
RJ45
Switch
PC
PC
Versorgungsspannung
Auxiliary Supply
I
2
I
3
I
N
L
1
L
2
L
3
L
N
I
5
I
6
24 V DC
C
Please ensure the correct setting of the current transformer, check the performance
values of the individual phases - these must not possess any negative signs when
drawing energy. Also check the power factor for plausibility. Turn the current
transformer if necessary!
Up to 2 residual current
measurements can be selected!
c
Attention! Fatal hazard due to electrical energy:
High voltage spikes that are dangerous to touch can occur on current transformers
that are driven with open-circuit secondary windings! For this reason, never operate
current transformers with open-circuit secondary windings!
First connect the current transformer lines to the corresponding measurement case
inputs!