background image

Technical Specifications

Safety and environmental conditions

CE marking

LV directive 2014/35/EU 
RoHS directive (EU) 2015/863

Standard

EN-IEC 61010-1:2010 
WEEE directive 2012/19/EU

This product is designed to be safe under the following conditions:

Location

Indoor use

Altitude

Up to 2000 m (1.24 mi)

Ambient temperature

-10 °C to +55 °C (14 °F to 131 °F)

Storage temperature

-20 °C to +70 °C (-4 °F to 158 °F)

Relative humidity

5% to 85%, non condensing

Pollution degree

2

Degree of protection

IP20

The CT27 is only suitable for insulated primary conductors.

Specifications

Standard

IEC 61869-2:2012

Rated short-time thermal 
current (Ith)

60 x Ipr / 1s

Rated dynamic current (Idyn)

2,5 x Ith

Continuous thermal current 
(Icth)

100%

Rated insulation level

0,72/3/- kV

Rated frequency

50/60 Hz

Class of insulation

A (105 °C / 221 °F)

Secondary terminal

Female clamping connector, 
suitable for conductor size: 
0,2 to 1,5 mm² solid, stranded
or ferruled (Strip length 8 to 
9 mm) (0.315 to 0.354 in)

Specifications per type

CT27

Secondary
leads format*

0,5 mm

2

max. 1,4 m

(55 in)

0,75 mm

2

max. 2,0 m

(79 in)

1,0 mm

2

max. 2,8 m

(110 in)

1,5 mm

2

max. 4,0 m

(157 in)

Suitable for 
cable

ø 7,5 mm (0.295 in)

Approximate
weight

40 g (0.088 lb)

* Maximum length secondary leads for 0,1 VA at the end of this leads.

Janitza electronics GmbH reserves the right to carry out modifications on 
its products, in order to improve them, without prior notice.

 

CT27 Current Transformer

Installation Guide

Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau | Germany
S49 6441 9642-22
[email protected] | www.janitza.com

Doc. No. 2.002.160.1.a | Issue date 06/2022 
Subject to technical alterration

Explanation of symbols

This product is designed according to the EN-IEC 
61010-1:2010 standards and therefore this product 
meets the requirements of the Low Voltage Directi-
ve 2014/35/EU.

Read the installation guide before mounting the 
product. Unprofessional work activities on electrical 
installations may result in a threat of danger to the 
life and health of human beings and livestock!

Under no circumstances the secondary circuit of 
the CT may be opened when the CT is mounted 
on a primary current and current is flowing in the 
primary circuit. High voltages may appear on the 
secondary leads when this circuit is left open.

RoHS Directive (EU) 2015/863

Janitza electronics GmbH states that they only uses 
qualified component in their products from ma-
nufacturers, whose specifications meet or exceed 
the requirements of the European Directive for the 
Restriction of use of certain Hazardous Substances.

WEEE Directive 2012/19/EU

The ‚crossed out wheeled bin‘ symbol indicates 
that the equipment should not be disposed as un-
sorted municipal waste. Contact a qualified recycler 
for disposal.

  

 

 

CT27-35
CT27-64

General

The CT27 is a current transformer and can only be used measuring 
electrical alternating currents. The CT27 is suitable only for moun-
ting on insulated primary conductors in a weather protected and 
dry location.