LX and LT Low NOx Pool/Spa Heater
Page 3
Any changes to the heater, gas controls, gas
orifices, wiring, draft diverter, or improper installation
may void the warranty. If change is required to any of
the above, consult the factory.
1.5 Technical Assistance
Consult Waterpik Technologies or your local
Jandy distributor with any questions or problems
involving the specifications, installation, and operation
of your Jandy equipment. An experienced technical
support staff is ready to assist you in assuring the
proper performance and application of Jandy products.
For technical support call the Technical Service
Department at (707) 776-8200 extension 260.
1.6 Materials Installer Must Provide
1.6.1 Materials for All Applications
The following items are needed and are to be
supplied by the installer for
all
LX/LT Low NOx
heater installations:
1.
The correct size gas pipe to supply gas from the
meter to the heater (see Section 4.1 ).
2.
A manually operated gas valve to be installed in
the gas line outside of the heater jacket.
3.
A suitable gas union joint to connect the heater to
the gas line outside of the heater.
4.
Plumbing items needed to provide a sediment
trap (drip leg) in the gas line between the manual
gas valve and the heater (see Section 4.1).
5.
A 115V AC or 230V AC power supply. A
junction box is not needed at the heater, connec-
tions are made inside of the heater jacket.
1.6.2 Materials for Special Applications
In addition to the items listed above, the follow-
ing items are needed for special applications.
1.
A factory authorized vent collar and any vent
pipe needed for indoor installations in the USA
and outdoor shelter installations in Canada (see
Section 3.3.2). Vent collars are available from
any Jandy distributor.
2.
Primer and cement suitable for cementing CPVC
pipe to PVC pipe and an appropriate coupling for
connecting the factory supplied CPVC pipe
nipples to PVC pool plumbing.
3.
A non combustible platform for installation on
combustible surfaces (see Section 2.3.3). Non
combustible bases are available from your Jandy
distributor.
1.7 Specifications
1.7.1 General Specifications
1.
Installation Location:
Certified for use:
In the USA:
Natural Gas:
Indoor and Outdoor
LP:
Indoor and Outdoor
In Canada:
Natural Gas :
Outdoor and Outdoor
Shelter
LP:
Outdoor and Outdoor
Shelter
2.
Minimum Clearance From Combustible Material:
See Table 2 in Section 2.3.2
3.
*Gas Pipe/Heater Gas Valve Connection:
Natural Gas:
3/4" NPT
LP:
3/4" NPT
*
For diameter of gas line from meter to heater see
Table 5 in Section 4.1.
4.
Supply Gas Type:
Certified for use with:
Natural gas and LP
5.
Inlet Gas Supply Pressure:
Minimum
Maximum
Natural Gas:
5.0 "WC
10.5 "WC
LP:
10.0 "WC
14.0 "WC
6.
Water Pipe/Heater Connection:
*2" Unthreaded PVC or CPVC
*Other size pipes may be used. See Section
5.5 for details
7.
Water Flow Rate:
Maximum:
125 gpm (475 lpm)
Minimum:
30 gpm (110 lpm)
8.
Working Water Pressure:
Maximum:
75 psi
9.
Exhaust Vent Connection Size:
Model:
250
7" Diameter
400
9" Diameter
10.
Electrical Supply:
Either 115 Volts AC or 230 Volts AC.
11.
Modification of Heater for High Altitude:
LX and LT Low-NOx are normally shipped
from the factory in the low altitude (sea level)
operational configuration. When requested, the
heaters can be configured and shipped for higher
altitudes. For field conversions to change altitude
configurations, manifold kits for mid altitudes and