Issue: 01.07.2020
Page 5
Specifications
Unit dimensions & weights
Electrical data & requirements
Outdoor unit sound spectrums
Unit Model
W x D x H
(mm)
Fixing Ctrs.
(mm)
Weight
(kgs)
Unit Model
W x D x H
(mm)
Fixing Ctrs.
Top (mm)
Fixing Ctrs.
Rear (mm)
Weight
(kgs)
BSCU-30-M1
77
BSCU-30-M3
76
BSCU-35-M1
97
BSCU-35-M3
96
BSCU-30-M1
77
BSCU-30-M3
76
BSCU-35-M1
97
BSCU-35-M3
96
BSCU-40-M1
107
BSCU-40-M3
107
826 x 122
826
(2x)
36
826 x 122
826
(2x)
38
63
2x JCC2-40E
865 x 505 x 489
745 x 122
CellarPlus 70-T1/T3
CellarPlus 80-S1/S3
1334 x 530 x 864
946 x 500
1x JCC2-80E
System
Outdoor Units
Indoor Units
1437 x 505 x 557
1173 x 324
1173 x 310
63
1173 x 310
CellarPlus 70-S1/S3
1108 x 478 x 649
703 x 448
1x JCC2-80E
1437 x 505 x 557
1173 x 324
745
(2x)
33
CellarPlus 80-T1/T3
1334 x 530 x 864
946 x 500
2x JCC2-50E
904 x 504 x 546
CellarPlus 90-T1/T3
1351 x 530 x 864
946 x 500
2x JCC2-60E
904 x 504 x 546
1108 x 478 x 649
703 x 448
Unit Model
Power
Supply
(V/ph/Hz)
Power
(kW)
MCC
(2)
(A)
LRA
(2)
(A)
RRC
(1)
(A)
SFR
(3)
(A)
Unit Model
Power
Supply
(V/ph/Hz)
Power
(kW)
RRC
(1)
(A)
SFR
(3)
(A)
BSCU-30-M1
230/1/50
21.5
82.0
12.2
25
BSCU-30-M3
400/3/50
10.3
40.0
5.1
16
BSCU-35-M1
230/1/50
25.0
97.0
14.0
32
BSCU-35-M3
400/3/50
9.0
46.0
5.7
20
BSCU-30-M1
230/1/50
21.5
82.0
13.3
25
BSCU-30-M3
400/3/50
10.3
40.0
5.4
16
BSCU-35-M1
230/1/50
25.0
97.0
14.3
32
BSCU-35-M3
400/3/50
9.0
46.0
5.8
20
BSCU-40-M1
230/1/50
28.0
114.0
17.4
40
BSCU-40-M3
400/3/50
11.0
50.0
6.8
20
(1) Power consumption and Rated Run Current (RRC) shown at nominal test condition (Troom 10ºC / 32ºC Ta) with R448A/R449A refrigerant
(2) Maximum Continous Current (MCC) and Locked Rotor Amps (LRA) are for the unit compressor only.
(3) SFR ~ Suggested Fuse Rating (Motor Rated for Outdoor Unit)
0.43
0.43
0.45
0.44
2.70
3.08
230/1/50
1.9
6
0.44
System
CellarPlus 70-S1/S3
CellarPlus 80-S1/S3
CellarPlus 70-T1/T3
CellarPlus 80-T1/T3
CellarPlus 90-T1/T3
2.90
3.17
3.65
Outdoor Units
Indoor Units
230/1/50
2.0
6
2.0
6
2.0
6
1.9
6
2x JCC2-50E
2x JCC2-60E
230/1/50
230/1/50
1x JCC2-80E
1x JCC2-80E
2x JCC2-40E
230/1/50
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
A (dBA)
A (dBA)
BSCU-30-M1/M3
62.1
56.7
51.3
48.2
43.1
38.3
31.3
54.1
34
BSCU-35-M1/M3
63.5
62.7
53.1
48.6
43.9
38.8
32.4
56.3
36
BSCU-40-M1/M3
61.4
61.7
58.6
55.2
51.7
48.3
43.1
60.7
41
Model
1/1 Octave Sound Pressure Levels @ 1 meter from front of the unit
Noise Levels
(10m)
Frequency
Содержание BSCU-30-M1
Страница 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 07 2020 CELLAR COOLER RANGE TECHNICAL MANUAL ...
Страница 8: ...Issue 01 07 2020 Page 8 Installation Quick Guide Piping Single System Twin System ...
Страница 24: ...Issue 01 07 2020 Page 24 Drawings Dimensional drawings Indoor Unit 80E ...
Страница 25: ...Issue 01 07 2020 Page 25 Drawings Dimensional drawings Outdoor Units BSCU 30 M1 M3 BSCU 35 M1 M3 ...
Страница 26: ...Issue 01 07 2020 Page 26 Drawings Dimensional drawings Outdoor Units BSCU 40 M1 M3 ...
Страница 28: ...Issue 01 07 2020 Page 28 Drawings Electrical wiring diagrams Outdoor BSCU 30 M1 BSCU 35 M1 BSCU 40 M1 ...
Страница 29: ...Issue 01 07 2020 Page 29 Drawings Electrical wiring diagrams Outdoor BSCU 30 M3 BSCU 35 M3 BSCU 40 M3 ...
Страница 33: ...Issue 01 07 2020 Page 33 Certification ...
Страница 34: ...Issue 01 07 2020 Page 34 THIS PAGE IS LEFT BLANK INTENTIONALLY ...