Standby mode
Only in combination with a suitable heat
pump and thermostat head for heating
and cooling
1
MODE
The device automatically enters the cooling mode as soon as the water temperature is 2
°
C lower
than the room temperature. If the water temperature is less than 1
°
C lower than the room tempera-
ture, the device will automatically switch to standby.
The device automatically enters the heating mode as soon as the water temperature is 4
°
C higher
than the room temperature. If the water temperature is less than 1
°
C higher than the room
temperature, the device will automatically switch to standby.
De breeze mode is switched on and off manually. The auto-change-over is disabled as long as the
breeze mode is active. Only applicable with control panel!
This device is not equipped with dew point control. This must be installed in the most critical place
by the installer! Condensing cooling due to a dew point control malfunction may damage the device
and its surroundings. !
3. OPERATION AUTO-CHANGE-OVER
3.1. FACTORY SETTINGS
The device is controlled via auto-change-over. The unit starts as soon as the set water temperature
has been reached. The user can temporarily select another mode manually.
Auto-change-over. The unit starts at the last selected speed(1, 2 or 3), as soon as the water
temperature > 28 ̊C.
Auto-change-over. The unit starts at the last selected speed(1, 2 or 3), as soon as the water
temperature < 24 ̊C.
The unit starts at the last selected speed (1, 2 of 3), regardless of the water temperature.
[B]
Option