EN
JAGA
ROOM THERMOSTAT
JRT-100
INSTALLATION , SETTINGS & USE
PRODUCT DESCRIPTION
TECHNICAL DATA
DIMENSIONS
CE MARK
MANUAL
JRT-100
/ 8751.050012
DEVICE INSTALLATION GUIDELINES
– 2-pipe and 4-pipe connection :
– 4-pipe connection : Heating / Cooling / Auto-change-over
– 2-pipe connection : Heating / Cooling
– automatic or manual fan speed control
– mounting on mounting box with screws
– programmable time zones (5+1+1): Monday - Friday (1-5), Saturday (6), Sunday (7)
– 0-10V exit
– valve control with 24V AC / DC thermoelectric motor
– possibility to run the fan once the“set point” has been reached (manual operation)
Important info : The unit must be installed by a certified installer in accordance with the installation instructions and the local building codes. Please
follow this instruction manual and file it somewhere safe! The unit must always be accessible for maintenance and inspection. . Jaga n.v. cannot be
held liable for damage due to non-compliance with this manual.
POWER SUPPLY
24V AC/DC
POWER CONSUMPTION
200 mA
SETTING RANGE
+10 ... +40°C
AMBIENT TEMPERATURE
0 ... +40°C
RELATIVE HUMIDITY
85% max
BACK-LIGHT
Blue
SENSOR
NTC 10K, 3950 ohm at 25 ° C
ACCURACY
+ 1°C (+0.5°C)
SAFETY CLASS
IP30
HOUSING
ABS with UL94-5 flame retardant plastic
1.5 m
Install the room thermostat at approximately 1.5
m above the floor against an interior wall and
opposite the heating source if possible. Avoid
the outer walls, draft coming from the windows
and doors, direct sunlight and other heat sour-
ces such as TVs, wall or table lamps, fire places,
heating pipes, etc. Ensure that the locking
mechanism on the bottom of the thermostat is
easily accessible.
The CE mark indicates hat this device meets the basic requirements of the directive on:
• EN 61000-6-3:2007+A1:2011
• EN 61000-3-2:2006+A1:2009+A2:2009
• EN 61000-3-3:2008
• EN 61000-6-1:2007
1.5
4.6
6
Mount the JRT.100 Room thermostat in a flush
mounting box with screw holes at a 60 cm
distance from the center. Minimum depth 45mm,
(the depth depends on the wiring). The internal
dimensions of the box should be at least Ø60mm
or 50x50mm.
M
8.6
8.6
6
1.4
3.4
www.jaga.com/downloads/
Briza/Manual_JRT100.pdf