34
CO2
PC / RF
INPUT: 110-240VAC
OUTPUT: 24V
N L
CO2
PC / RF
INPUT: 110-240VAC
OUTPUT: 24V
N L
4.2.3. Factory reset
1.
Disable power charge .
2.
Press and hold down both the [-] and [+] button on the circuit board
and switch on the power again.
The blue LED
will light up, followed
by
the green LED
2 seconds later and
the red LED
4 seconds later.
Release the buttons as soon as all 3 LEDs are flashing .
3.
The controller will return to the Factory settings, all LEDs will flash for 10 seconds. The controller
will return to the Factory Default settings, all LEDs will flash for 8 seconds .
4.
Make sure that the rotary DIP switch is in the correct position !
4.2.4. Circuit board error code
4.2.5. Control panel error codes
Error sensor [Tw of To] - Check the water
temperature sensor
Error sensor [Tw / To] - Check the water temperature sensor
Error sensor [Tr] - Check the room tempe-
rature sensor
CO2
PC / RF
INPUT: 110-240VAC
OUTPUT: 24V
N L
DPC.BR712 / DPC.BR722 / DPC.BR724:
position 7
DPC.BRC42 / DPC.BRC62 / DPC.BRC64
: position C
Error sensor [Tr] - Check the room temperature sensor