Jafar 1350 Скачать руководство пользователя страница 3

 

OPERATION AND MAINTENANCE MANUAL

 

01-2016 

 

3

1 TECHNICAL DESCRIPTION 
 
1.1 PRODUCT DESIGNATION AND IDENTIFICATION 

 

The subject of this Operation and Maintenance Manual is

Type BA reduced pressure zone antipollution (anticontamination) check valves. 
 
 

1.2 USE 
 
The P/N 1350 type BA low-pressure antipollution (anticontamination) check valves are intended for 

protecting building water supply systems from contamination backflow within the pressure range from 0.05 MPa 
to 1.6 MPa and temperatures up to +70ºC. 

 
1.3 TECHNICAL SPECIFICATION 

 

The P/N 1350 type BA low-pressure antipollution (anticontamination) check valves  

are intended to protect water supply systems from contamination with backflow liquids. 

 

- Available diameters: 

DN65-DN250 

- Max medium flow rate:   

 

4 m/s; 

- Max operating pressure (PS): 

 

1.0 MPa 
1.6 MPa 

- Max operating temperature (TS):   

70ºC. 

 

The valves are designed according to PN-EN 12729: 2005, a product standard for 

devices which  

protect  potable  water  from  backflow  contamination,  controllable  backflow  preventer  with  a  reduced  pressure 
zone, family B, type A. 

 

A  distinct  feature  of  the  Type  BA  antipollution  check  valves  is  a  two-chamber  design  which  allows 
isolating  the  incoming  medium  flow  and  automatic  removal  of  medium  residues  from  the  reduced 
pressure chamber. 

 

Protection against pollution of potable water in water installations and general requirements  

of devices to prevent pollution by backflow are explained in PN-EN 1717: 2003, where type BA valves can be 
controllable and protect potable water supply installations from pollution with Category 2 liquids. 
 

Antipollution valves can be used as check valves in indoor installation only when placed  

between a water meter and the receiver(s) and generally in horizontal pipelines. The valve body features a flow 
direction arrow.  

The valve connection flange design is acc. to PN-EN 1092-2: 1999, with the sizes compliant with the  

nominal pressure values. 
 

Nominal PN pressure: 

 

 

 

- 0.6 MPa 

- 1.0 MPa 
- 1.6 MPa 

 

Installation length of flanged and bell socket tapped antipollution valves:  

- see the size table. 
 
 
 
 
 

 

Содержание 1350

Страница 1: ...50 Approved for use by President of Factory JAFAR S A Failure to comply with the guidelines and instructions in this Operation and Maintenance Manual releases the manufacturer from all obligations lia...

Страница 2: ...2 MATERIALS 6 2 3 DIMENSIONS 7 2 4 REFERENCE STANDARDS 8 2 5 ORDERING INFORMATION 8 2 6 PRODUCTION AND ACCEPTANCE 8 2 7 MARKINGS 9 3 PROTECTION STORAGE TRANSPORT 9 3 1 PROTECTIVE COATINGS 9 3 2 PACKA...

Страница 3: ...h protect potable water from backflow contamination controllable backflow preventer with a reduced pressure zone family B type A A distinct feature of the Type BA antipollution check valves is a two c...

Страница 4: ...located at the valve body bottom The chamber over the membrane disk is open to the valve inlet chamber The chamber under the membrane disk is the central zone between the inlet and the outlet ends an...

Страница 5: ...OPERATION AND MAINTENANCE MANUAL 01 2016 5...

Страница 6: ...ISO 1629 2005 10 11 23 Gasket EPDM PN EN ISO 1629 2005 12 Head POM Manufacturer s catalogue 13 Drain valve poppet POM Manufacturer s catalogue 14 Drain valve poppet guide POM Manufacturer s catalogue...

Страница 7: ...3 DIMENSIONS DN L H D d K PN16 PN10 I PN16 PN10 n PN16 PN10 Weight kg 65 356 150 185 122 145 80 440 155 200 138 160 30 0 100 530 180 220 158 180 150 630 210 285 212 240 200 765 240 340 268 295 12 8 25...

Страница 8: ...cap screws PN EN 10204 2006 Metallic products Types of inspection documents PN ISO 1629 2005 Rubbers and latices Nomenclature PN EN 1717 2003 Protection against pollution of potable water in water ins...

Страница 9: ...ting Polish Construction Mark B and or the CE mark as applicable product type 3 PROTECTION STORAGE TRANSPORT 3 1 PROTECTIVE COATINGS All inner and outer cast iron surfaces are protected with electro d...

Страница 10: ...erature and pressure The valve assembled and delivered by the manufacturer is ready for installation Disassembly of the valve components without proper care may result in loss of integrity 4 2 ASSEMBL...

Страница 11: ...f the valve The installation site and method shall assure free access for maintenance and servicing Do not install the valve in a location exposed to flooding The product shall not be exposed to tempe...

Отзывы: