background image

SYSTEM SETUP 

SYSTEM SWITCH SETTINGS 

There are twelve, two-position slide switches located on the control panel. Set applicable switches in their proper 

position for HVAC equipment configuration and control options. 

    ON          OFF 

HP         HC       SYSTEM 

  FOSSIL      CONV     HEAT PUMP 

  B         O         REV  VALVE 

  ELEC      GAS     FAN 

  ZONE      ALL      FAN MODE 

  1 MIN      OFF      PURGE 

  20 MIN     OFF      TIME SHARE 

  MAJORITY  COOL      PRIORITY 

TIME SHARE 

Time Share can be used with either the Cooling Priority Mode or Majority Wins Mode. If zones being served 

(heating or cooling) have not been satisfied within 20 minutes and an opposite call takes place, the system will 

changeover. When that mode is satisfied or 20 minutes has gone by, the system will again changeover if an 

opposite call exists. 

FAN MODE 

When the Fan Mode slide switch is set in the ALL position and at least one zone thermostat is set in the fan ON 

mode, all zone dampers will open for ventilation air between equipment calls. When the Fan Mode slide switch is 

set in the ZONE position, only those zone thermostats set in the fan ON mode will have their dampers open for 

ventilation air between equipment calls. 

CAPACITY CONTROL SETTINGS 

The three Capacity Control slide switches have a numerical value of 2, 3 and 4. Any switch or combination of 

switches set in the ON position establishes the Capacity Control value. This value equals the minimum number of 

zones that must be calling in the same mode before a second stage 

can be 

energized. Capacity Control only 

allows for the upstaging to occur; it still requires a second stage call from the thermostat or Stage Timer to actually 

initiate the second stage of the equipment. It is recommended that the Capacity Control value equal no more than 

50% of the total number of zones. This feature works with multi-stage and single-stage thermostats. The Stage 

Timer must be ON when single-stage thermostats are used with multi-stage equipment.   

STAGE TIMER 

The Stage Timer switch is located below the Capacity Control switches. When the switch is set in the ON  

position, the adjustable Stage Timer is activated. This feature allows for the use of single-stage zone 

thermostats with multi-stage and heat pump equipment. The Stage Timer can be set from 5 to 20 

minute upstaging. (Typically set at 10 minutes)  

ADJUSTABLE LIMITS 

High Limit (Z-600-DAS Sensor) - Set at 170° for conventional heating systems and dual fuel applications. Set at 

120° for heat pump. Allows fan to run but shuts off or down-stages equipment to prevent overheating. 

Low Limit (Z-600-DAS Sensor) - Adjustable from 40° to 58° for both heat pump systems and conventional air con-

ditioning. Allows fan to run but shuts off or down-stages equipment to prevent the coil from freezing. 

Low BP (Z-600-OTS Sensor) - Set balance point to prevent heat pump operation when outdoor temperature 

falls below setpoint. (Typically set at 35° F) 

High BP (Z-600-OTS Sensor) - Set balance point to prevent fossil fuel heat operation when outdoor temperature 

rises above setpoint. (Typically set at 55° F)

DEFINITIONS 

HP        Heat pump equipment 

HC        Conventional heating and cooling equipment 

FOSSIL      Heat pump with fossil fuel furnace 

CONV        Heat pump with or without electric auxiliary heat 

B          Heat pump reversing valve energized in heating 

O         Heat pump reversing valve energized in cooling 

ELEC        Fan energized on call for heat 

GAS       Fan controlled by furnace 

ZONE        Ventilation controlled by individual zone thermostat  

ALL        Ventilation for all zones when any zone thermostat is set on continuous fan 

1 MIN        Fan purges to last zone calling for 1 minute (Do not use with constant fan)

20 MIN       20 minute Time Share used with Majority Wins or Cooling Priority mode 

MAJORITY    Heating and cooling controlled by greatest demand 

COOL        Cooling calls receive priority over heating calls 

CAPACITY

CONTROL 

CAPACITY CONTROL VALUES 

       

2 ON     =  2 Zones            2 & 4 ON    =  6 Zones 

      3 ON     =  3 Zones            3 & 4 ON    =  7 Zones 

      4 ON     =  4 Zones            2, 3 & 4 ON  =  9 Zones 

       

2 & 3 

ON  =  5 Zones 

5418 Elmwood Avenue, Indianapolis, IN  46203-6025 

Toll Free:  888.652.9663   Fax:  317.227.1034 

www.jacksonsystems.com 

06-1007-021109

4 ZONES      OFF 

3 ZONES      OFF 

2 ZONES      OFF 