The low limit (FS-38)  should be wired to 
the “LL” terminals on the control panel 
(remove jumper).  The compressor will 
shut off when low limit trips out. 

 

The high limit (HL-170-HP) should be 
wired to the “HL” terminals on the panel 
(remove jumper). The compressor, auxil-
iary heat and emergency heat will shut 
off when the high limit trips out. 

 

A 40 VA transformer will power the con-
trol panel and up to four (4) dampers. 
A 75 VA transformer will power the con-
trol panel and up to seven (7) dampers. 

 

Up to three (3) dampers can be connected 
in parallel.  A total of no more than seven 
(7) dampers may be connected to the sys-
tem.  A system may be a single panel or 
multiple panels. 

 

If more than three zones are required, two 
additional control panels can be used to 
control up to a total of nine (9) zones.  T5 
terminal strip is used only when more 
than three zones are required. 

 

Label the dampers, damper wires and 
thermostat wires with the zone number 
and the area they serve. 

Manual Changeover 

Installation Notes: 

To install the panel, first slide the PC 
board out of its base and screw the base 
to a flat surface next to the HVAC 
equipment.  The PC board should be 
reinstalled by centering it over the base 
and pushing firmly. 

 

Connect only 24

 

Vac to Control Panel. 

 

The zone control panel requires a sepa-
rate 24 Volt transformer. 

 

No special wire is required.   

 

The thermostats and motorized dampers 
may be located up to 300 feet from the 
control panel when using 18 gauge ther-
mostat wire. 

 

Fuse F1 (4 Amp) protects the relay con-
tacts.  Fuse F2 (4 Amp) protects the 
printed circuit board. 

 

Zone dampers are powered closed / 
spring return open. 

 

If the heat pump is not equipped with 
short cycle protection, a short cycle pro-
tection timer (TD-5) should be installed. 

Specifications:

 

Panel Dimensions: 
Height: 5.0 inches 
Width: 10.0 inches 
Depth: 2.0 

inches 

 

Mounting: 
2 back plate screws 

 

Operating Ambient Temperature: 
-20º to 160º F 

 

Power Supply: 
24 Vac 40VA / 75VA transformer 

 

Terminal Designations: 

W = 

Auxiliary Heat 

EH =   Emergency Heat 
Y =  

Compressor 

G =  

Fan 

O =  

Changeover Valve 

R =  

Hot 24 Volt 

X =  

Common 

D =  

Damper 

LL =   Freeze Stat 
HL = 

High Limit 

H =  

Hot 24 Volt 

G =  

Ground or Common 

Comfort System

  

Wiring Diagram For Z-300-HP Heat Pump Zone Control Panel 

05-13-05 

www.jacksonsystems.com 
[email protected] 

When 

green

 zone LED’s 

are on, those zones are  
calling for heating or 
cooling. 
 
If the thermostat does not 
have an “EH” terminal, 
disregard “EH” on the 
zone panel. 
 

All thermostats must 
be set in the same 
mode

.

 

Website: 

E-mail: 

888.652.9663 
317.227.1034 

Toll-Free: 

Fax: 

Отзывы: