The JA-80S wireless fire detector 

 

MHS51500FCC 

Jumper  position  =  FIRE  =  the  control  panel  responds  with  a  fire 
alarm, no matter if the system is armed or not. 

 Jumper  position  =  INST  =  the  control  panel  responds  with  a  fire 
alarm  only  if  the  system  is  armed.  The  alarm  is  not  indicated  by  an 
internal LED. This feature is useful if the user wishes to allow smoke 
in  a  room  from  e.g.  smoking  or  a  fireplace,  while  the  control  panel  is 
disarmed when authorized people are present in the building. 
Warning: In the INST position, while the system is disarmed, it is not 
protecting against fire. The FIRE / INST jumper only has an effect if the 
detector  has  a  natural  reaction  assigned  to  its  address  in  the  Oasis 
control panel.  It also has no effect when used with a UC-8x or AC-8x 
receiver.  Whenever  the  detector  cover  is  opened,  a  tamper  signal  is 
sent. 

  

   Testing the detector  

The  functioning  of  the  detector  can  be  tested  by  pressing  and 

holding the test button (e.g. for 1 sec).  This activates the siren and the 
LED  flashes  (LED  only  if  the  fire  reaction  is  set).  The  strength  and 
quality  of  detector  signals  can  be  measured  by  the  control  panel  in 
Service mode. During testing by the test button, the detector transmits 
signals which can not trigger fire alarms in the control panel.  

Warning:  Never  start  a  fire  in  a  building  to  test  the  detector

Instead, use smoke-simulating aerosols for realistic testing. 

Silencing the siren during an alarm 

During a fire alarm, the detector LED flashes (if the fire reaction is set) 

and the built-in siren sounds. Under these conditions the siren can be 
silenced by pressing the test button, but the LED will continue to flash 
until the smoke clears from the room.  

Alarm memory in the detector 

Normally the detector’s fire-alarm condition lasts until the smoke clears 

from  the  room  and  the  fire-alarm  information  is  stored  in  the  control 
panel‘s memory. If desired and the fire reaction is set, a local memory 
in the detector can be enabled by pressing and holding the test button 
during  battery  installation.  If  this  function  is  enabled,  after  detecting 
fire,  the  detector‘s  fire  alarm  mode  continues  until  the  test  button  is 
pressed. 

Fault indication 

The  detector  performs  regular  self-testing. If  a fault  is  detected  in the 

detector,  its  LED  will start  to  flash  rapidly.  In  such  a case,  disconnect 
the battery from the detector, and after about 20 secs, re-connect it. If 
after  a  minute  the  LED  still  flashes,  then  send  the  detector  off  for 
repair. 

Battery replacement 

The detector monitors its battery voltage and if too low, a transmission is 
sent  to  the  control  panel  to  inform  the  installer  or  user.  The  detector 

continues  to  function  but  with  a  short  LED  flash  every  minute.  Battery 
replacement should not be delayed by more than two weeks. This should 
be done by a qualified technician with the control panel in Service mode. 
After  battery  replacement,  test  the  functioning  of  the  detector  using  its 
test button. Expired batteries should not be thrown into the garbage, but 
disposed of according to local regulations. 

 

Removing the detector from the system 

 

If  a  detector  is  removed,  the  control  panel  announces  the  removal. 

The  detector  has  to  be  deleted  in  the  control  panel  before  intentional 
removal.

 

Technical parameters 

Voltage: 

Lithium battery type CR14505 (AA 3.0V) 

Typical battery lifetime 

approx. 3 years 

Communication band 

868 MHz, Oasis protocol 

Smoke detection 

optical, light dispersion 

Smoke sensor sensitivity 

 m = 0.11 

÷

 0.13 dB/m to EN 54-7 

Temperature detection 

class A2 to EN 54-5 

Fire-alarm temperature 

+60 °C to+ 70 °C  

Acoustic power of the built-in siren 

80 dB/m A   

Operational temperature range 

-10°C to +80 °C 

 Dimensions  

diameter: 126 mm, height: 65 mm 

Complies  with  EN  54-7,  EN  54-5,  prEN  54-25,  ETSI  EN  300220,  

EN 50130-4, and EN 55022, EN 60950-1, ANSI C63.4 

Can be operated according to 

ERC REC 70-03, FCC Part 15 

FCC ID VL6JA80S 
 

 

 

Jablotron  Ltd.  hereby  declares that  the JA-80S  is  in compliance  with  the 

essential  requirements  and  other  relevant  provisions  of  Directives 
1999/5/EC,  1989/106/EC 

and  complies  with  part  15  of  the  FCC  rules. 

Operation  is  subject  the  the  following  two  conditions:  1.  This  device  may  not 
cause  harmful  interference,  and    2.  this  device  must  accept  any  interference 
received, including interference that may cause undesired operation.

 The  original  of  the  conformity  assessment  can  be  found  at 

www.jablotron.com

,  Technical  support  section

  CAUTION:  Changes    or 

modifications  no  expressly  approved by  Jablotron  could void  the user´s  authority  to 
operate the equipment

 

 

 

 Note:  Although  this  product  does  not  contain  any  harmful 
materials  we  suggest  you  return  the  product  to  the  dealer  or 
directly to the producer after use.

 

 
 

 

 