The JA-80S wireless fire detector 

 

MHS51500FCC 

 

The JA-80S wireless fire detector  

 

The JA-80S is a component of Jablotron’s Oasis 80 alarm system. It 

is  designed  to  detect  the  presence  of  fire  inside  residential  or 
commercial  buildings. It  should  not  be  installed  in industrial  premises.  
The battery-powered detector communicates via OASIS radio protocol 
and has a built-in local warning siren. 

The detector combines an optical smoke sensor with a heat sensor. 

Both sensors have their outgoing signals processed digitally, resulting 
in higher false alarm immunity. The optical sensor works using a light 
diffusion  principle  and  is  very  sensitive  to  the  presence  of  large-sized 
particles  which  are  characteristic  of  dense  smokes.  By  contrast,  the 
sensor  is  less  sensitive  to  small-sized  particles  which  are  typical  of 
cleanly burning fires. In particular, the smoke sensor is not capable of 
detecting the by-products of cleanly-burning fluids such as alcohols, for 
instance,.  This  deficiency  is  compensated  for  by  the  built-in  heat 
sensor. This sensor provides a slower reaction when compared to the 
smoke sensor, but is much better at reacting to fires with rapidly rising 
heat producing only a little smoke. 

Exposing  fire  conditions  to  the  smoke  and  heat  sensors  requires 

some level of air circulation. It is therefore necessary to install the JA-
80S  detectors  in  such  a  place  on  the  ceiling  that  (in  the  case  of  fire) 
smoke  masses  are  forced  to  go  in  the  direction  of  the  detector’s 
position. This can usually be achieved in most buildings. However, the 
JA-80 is not suitable for installation in outdoor spaces or interiors with 
an  extremely  high  ceiling  where  fire  by-products  would  not  reach  the 
detector position. 

Detection range, detector positioning 

The following table shows the detector’s working range in relation to 

the height of the ceiling on which the detector is installed. The range is 
expressed as the radius of the circular fire detection area for a detector 
installed on a ceiling directly above . 

 

Ceiling height (m) 

 

< 4.5 

4.5-6 

6-8 

8-11 

11-25 

> 25 

Smoke  
detection 

7.5* m  7.5* m 

7.5* m 

7.5* m 

Not suitable 

Not 

applicable 

Heat 
detection 

5* m 

5* m 

5* m 

Not 

suitable 

Not 

applicable 

Not 

applicable 

Not applicable – meant for a particular ceiling height range 
Not suitable –not usually used in such cases 
* – the radius of the detection area below the detector
 

 
Installation on a horizontal level ceiling  
Due  to  the  possible  occurrence  of  a  cold  air  layer  right  under  the 

ceiling,  the  detectors  must  not  be  imbedded  into  the  ceiling.  The 
distance  between  any  point  to  be  protected  and  an  imaginary  vertical 
line  from  the  detector  down  to  the  floor  must  not  exceed  the  radius 
indicated in the table. 

 
Installation on a sloping ceiling 
If the JA-80S is installed just under an apex formed by the joining of 

two sloping ceilings the values indicated in the table can be increased 
by  1%  for  every  degree  of  slope  up  to  a  maximum  of  25%.  If  the 
space  to  be  protected  is  under  a  saw-tooth  type  of  roof,  JA-80S 
detectors should be installed under each apex. However, a roof with a 
shallow  saw-tooth  form  can  be  acceptable  if  the  height  difference 
between  the  highest  and  lowest  parts  of  the  ceiling  does  not  exceed 
5% of the total ceiling height. 

 
Walls, partitions, obstacles, and trussed ceilings 
The  JA-80S  must  not  be  installed  closer  than  0.5  m  from  any 

wall  or  partition.  A  narrow  room  with  a  width  of  less  than  1.2m 
requires the detector(s) to be placed at a distance of at least one third 
of  the  room’s  width  away.  In  the  case  of  separating  walls  (partitions, 
warehouse  objects)  which  do  not  reach  the  ceiling,  the  space  is 
considered to be fully separated if the gap between the top of the 
separating  wall  and  the  ceiling  does  not  exceed  0.3  m
.  A  free 
space  of  at  least  0.5m  is  required  under  the  detector.  Irregularities  in 
ceiling shape which do not exceed 5% of ceiling height are considered 
insignificant  –  the  ceiling  can  be  regarded  as  being  even  and  limits 
from  the  table  are  applicable.  However,  any  irregularity  (including 
beams)  exceeding  5%  of  the  ceiling  height  is  considered  to  be  a 
wall with the consequences stated above

 
Ventilation and air circulation 
The detectors must not be installed directly by a fresh air inlet

e.g. air conditioning vents. In the case of air being supplied through a 
perforated ceiling, each detector must be placed so that no perforation 
hole occurs within 0.6m of the detector. 

Avoid installing the detector in the following locations: 

 

Places  with  poor  air  circulation  (niches,  corners,  apexes  of  A-
shaped roofs). 

 

Places exposed to dust, cigarette smoke or steam. 

 

Places  with  over-intense  air  circulation  (close  to  ventilators,  heat 
sources or air conditioning outlets). 

 

Kitchens and other cooking places (because steam, smoke or oily 
fumes can reduce detector sensitivity). 

 

Places  close  to  metal  objects  (which  can  cause  radio 
communication screening). 

 
Caution:  The  most  common  reason  for  the  detector  to  be 
accidentally triggered is improper detector location. 

 

open

c

lo

s

e

   

test
button
with LED

 

 

Installation 

Take the following steps: 

1.  Open the detector (rotate the rear cover)  

2.  Screw the rear  cover onto the desired location 

3.  Leave  the  battery  disconnected  and  the  cover  open  and  then 

follow the control panel or receiver manual. 

4.  The basics of enrollment are: 

1.  Enter  enrollment mode  on the  control  panel  by  keying  in  “1”  in 

Service mode.  

2.  Install a battery into the detector to activate enrollment and self-

calibration (20 secs) which should be done in clean air  without 
smoke or fumes at a temperature of about +20°C.  

3.  Exit enrollment mode by pressing “#”. 

4.  To  enroll  a  detector  after  having  already  connected  a  battery, 

first  disconnect  the  battery,  and  press  and  release  the  test 
button  to  discharge  any  remaining  charge  to  ready  the  device 
for enrollment.  

5.  After  closing  the  detector,  check  that  the  two  halves  of  the 

housing are securely together. 

After  installing  a  battery  into  the  detector,  allow  one  minute  for 

stabilisation. During this minute the LED is continuously lit.  

Jumpers 

Fire

Instant

 

 

SIREN  ON  /  OFF  allows  the  built-in  siren  to  be  disabled  (OFF  = 

disabled) 

FIRE / INST selects what the natural reaction of the control panel to 

the detector signal will be. 