The JA-121T BUS RS-485 interface 

The JA-121T BUS RS-485 interface 

1 / 3 

MNN51110 

The JA-121T is a BUS component of the 

JABLOTRON

 system.  

It is a universal converter which interfaces communication between 

the system BUS and the RS-485 serial line and vice versa. For 

example, it is suitable for instant connection of a smart  home 

systems thus giving you the possibility to fully use the features of 

both systems. It includes galvanically separated circuits protecting 

the device against up to 4kV. Data is sent during a status change 

or when requested. The module is addressable and takes one 

position in the system. The module should be installed by a trained 

technician with a valid certificate issued by an authorised 

distributor. 

Installation 

1. Attach the module to an appropriate place, in the range of the

JABLOTRON 100 BUS and RS-485 serial line. We recommend

using a JA-190PL installation box and utilizing a spring on the

LEARN button (5) – used as a tamper contact.

2. If the module is placed in a different box with its own tamper

protection, use the TMP contacts (3). After enrolling the module

in the control panel, you can select a type of tamper protection

(the LEARN button or the TMP contact).

3. Connect the wires to the RS-485 (6) output terminals including

the common power supply which serves to supply the serial

line.

Figure 1: 1 – BUS terminals; 2 – production code (sticker on the BUS 

terminals); 3 – TMP terminal; 4 – yellow LED; 5 – LEARN (enrollment) button 

(tamper – spring is included); 6 – galvanically separated RS-485 BUS output 

When connecting the module to the system 

BUS, always switch the power off. 

4. Connect the BUS cables to the terminals (1).
5. Proceed according to the control panel installation manual.

Basic procedure:
a. When the system is switched on, the yellow LED (4) starts

flashing repeatedly to indicate that the module has  not

been enrolled into the system yet.

b. Go to the 

F-Link

  software, select the required position in

the 

Devices

  tab and launch the enrollment mode by

clicking on the 

Enroll

 option.

c. Click on the option 

Scan/add new BUS devices

, select

the JA-121T module and double-click to confirm selection – 

the yellow LED indicator (4) goes off.

6. Close the cover of the installation box with the module.

Notes:

It is possible to enroll the device by pressing the front LEARN

button (5).

The detector can be enrolled by entering the production code

(2) in the F-Link software (or using a bar code reader). Enter all

digits located below the bar code (1400-00-0000-0001).

If you want to remove the detector from the system, erase it

from its position in the control panel.

Terminal mode – function description 

The communication of the RS-485 serial line is coded in ASCII, 

speed 9600 baud, 8N1 (8 data bits, no parity, 1 stop-bit). Control is 

realized by the following commands; the valid syntax is 

code

 space 

command

List of commands: 
VER

 

Returns the JA-121T module version. 

HELP

 

Returns help (valid commands and also examples of 

correct syntaxes). 

SET

 

Sets selected sections: a command followed by digits 

representing the sections which are to be set – each 

digit always has to be separated by  a space. When 

sections are not specified, the system is completely 

set. 

SETP

 

Sets partially selected sections: a command followed 

by the digits representing the sections which are  to 

be set partially –  each digit always has to be 

separated by a space. When sections are not 

specified, the system is set partially i.e. all sections 

which have partial setting enabled. 

UNSET

 

Unsets selected sections: a command followed by 

digits representing the sections which are to be unset 

– each digit always has to be separated by a space.

When sections are not specified, the system is unset

completely.

PGON

 

Activates PG outputs: the reference numbers of the 

PG outputs you want to activate must be added after 

the command. Each digit always has to be separated 

by a space. 

PGOFF

 

Deactivates PG outputs: the reference numbers of 

the PG outputs you want to deactivate must  be 

added after the command, each digit always has to 

be separated by a space. 

Commands 

SET, SETP, UNSET, PGON 

and 

PGOFF

  cannot 

control sections or PG  outputs for which the used code does not 

have access rights. 

STATE

 

Returns the states of sections: a command followed 

by the digits representing sections of which status 

you want to check  –  each  digit always has to be 

separated by a space. When sections are  not 

specified, the system always returns the status of all 

sections. 

PGSTATE

  Returns the state of PG outputs: a command followed 

by the digits representing the PG outputs of which 

status you want to check – each digit always has to 

be separated by a space. When the PG outputs are 

not specified, the system always returns the status of 

all PG outputs. 

FLAGS

 

Returns the active indexes in sections: the reference 

numbers of the sections you want to check the 

indexes for can be added – each digit always has to 

be separated by a space. When sections are not 

specified, the system always returns  the indexes of 

all sections. 

PRFSTATE

  Returns  the status of all devices  in HEX code, for 

details  it is necessary to convert it to BIN code 

(1 – active, 0 – inactive). 

Examples: 

The command has to be in a specific order: valid code (with 

prefix), command and additional information (list of sections which 

can be set, PG outputs which can be turned off, and so on). 

Each 

command must end with an ending character (Enter).

  

The entered code is used as a system user therefore it is recorded 

in the event history and possible restriction linked with the user’s 

code may be applied. 