background image

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

The JA-111TH BUS temperature detector

The JA-111TH BUS temperature detector

MNG51205

The JA-111TH is a component of the 

JABLOTRON 100

system.

It serves for temperature measurement and forwarding measured data 
to MyJABLOTRON. MyJABLOTRON manages and stores measured 
data for further use, for instance activating a selected PG output,
the SMS reporting of exceeding temperature limits or to create graphs
of measured temperatures. All functions are programmable directly
in MyJABLOTRON. The PG control function can be assigned 
to a maximum of 2 thermometers per control panel. This product should
be installed by a trained technician with a valid certificate issued 
by an authorised distributor. 

Installation

Select the installation place according to the temperature measuring 

requirements. It is not recommended to install the detector near heat 
sources affecting measuring (heaters, electric fans, air conditioning 
outlets, fireplace inserts, etc.). The detector can also be installed 
in an outdoor environment but it has to be placed into a suitable box 
with a minimum of IP65 housing, the JA-192PL-A for example.

Figure 1: 1 – cover tab; 2 – LED indication

1. Open the detector cover by pushing the tab (1).
2. Punch though the holes for the BUS cable in the plastic base. 
3. Insert the BUS cable and attach the plastic base to the required

place using screws.

When connecting the detector to the system BUS, 
always switch the power off.

4. Connect the BUS cables to the terminals (6).

Figure 2: 3 – Jablotron system BUS; 4 – red LED indicator;

5 – yellow LED indicator; 6 – BUS terminals; 7 – production code;

8 – LEARN (enrollment) button; 9 – measurement sensor

5. Proceed according to the control panel installation manual. 

Basic procedure:
a. When the device is switched on, the yellow LED (5) starts 

flashing repeatedly to indicate that the module has not been 
enrolled to the system.

b. Go to the 

F-link

software, select the required position in the 

Devices

tab and launch the enrollment mode by clicking on the

Enroll

option.

c. Click on 

Scan/add new BUS devices

, select the JA-111TH 

detector and double-click on it to enroll it - the yellow LED 
indicator (5) will shut down.

6. Close the detector cover. 

Notes:

Enrolling the detector to the system is possible by pressing 
the LEARN button when the enrollment mode is activated 
or by entering the production code (7) via the F-Link software.
All digits in the production code are required (1400-00-0000-0001).

If you want to remove the detector from the control panel, erase it 
from its position 

Functions

The JA-114E and JA-154E series of keypads are able to display 

up to 2 current temperatures on the keypad screen. See the JA-10xK 
installation manual.

The detector has a fixed antifreeze temperature of +6 °C with ±1 °C 

hysteresis. Therefore the detector has an activation temperature 
of +5 °C. The deactivation temperature is +7 °C.

Using the F-Link software, it is possible to configure the JA-10xK

control panel’s reaction (PG output, 24h alarm, etc) to react 
to temperature detector activation. Thus the selected PG output 
is controlled directly by the control panel.

All thermometer functions can be fully used in MyJABLOTRON. 

The registration procedure is described in the

Control panel installation 

manual.

Note:

The red LED (4) always flashes when the periodical temperature 
is measured and when the activation or deactivation temperature
(6 °C) has been reached.

MyJablotron

All thermometers and their measured values are stored and shown

in the

Thermostats and Thermometers

tab in MyJABLOTRON.

The temperatures are stored automatically every 5 minutes.
The temperatures are displayed in a graph with an adjustable timeline.
It’s possible to export data from the graphs in various formats for further 
processing. The graph function enables you to compare temperatures 
from two thermometers or different time periods (only available 
in the MyJABLOTRON mobile app).

The app offers the following functions:

PG control by measured temperature

Using MyJABLOTRON, it’s possible to configure activation of a PG 

output by a temperature measured by the thermometer. The selected 
PG output is controlled remotely from MyJABLOTRON therefore stable 
external communication is necessary for this function to work properly.
If this function is selected, the user can use a slider to configure 
the desired temperature which will activate the PG output. These 
settings are located in the 

Thermostats and Thermometer

tab.

Linking the thermometer with a PG output is done by a service 

technician in the 

Installation management

section

of

the

MyCOMPANY app. Select the control panel, enter the 

Devices

tab,

press the symbol of a gearwheel on the thermometer and select a PG
output which should be controlled by the measured temperature. 
Use the slider to configure the desired activation temperature. 
This configured link is indicated by a PG symbol at the thermometer’s 
position.

Warning

!

The controlled PG output must be configured to have 

ON/OFF

or 

Impulse

functions (configurable in the F-Link software). 

Notes

:

Establishing the link and controlling the PG output by the measured
temperature can also be done in the MyCOMPANY and
MyJABLOTRON mobile app.

This function can be configured for a maximum of 2 thermometers 
enrolled to the control panel (the sum of wireless and BUS 
thermometers).

Connection via GSM and LAN communicators is required in order 
to make sure that PG output control from MyJABLOTRON works 
properly.

Due to fact that PG outputs are controlled via an external app,

we cannot guarantee proper functioning under all 
circumstances

. When the connection with MyJABLOTRON is lost, 

the status of the PG output stays unchanged until the connection 
is re-established. This is why we recommend using a controlled PG 
output along with the IMPULS function set to an activation time 
of 2:00:00. The PG output will be controlled by commands from 
MyJABLOTRON. If the connection is lost, activation of the PG
output will be limited by the activation time of the IMPULS function.

The activation hysteresis of a PG output is +/- 1°C. The PG output 
will be activated when the measured temperature is 1°C lower than 
the activation temperature. Deactivation will occur when this 
temperature is exceeded by 1°C.

Notifying the user when the temperature exceeds the allowed 
range

You can set a higher and a lower temperature limit and a certain 

period of time of temperature monitoring for a selected thermometer 
in 

Settings 

Æ

Thermometer notification

. When one of these limits 

is exceeded or gone below then it’s reported by an SMS, an e-mail
or push notifications if you use the MyJABLOTRON app.

Отзывы: