JA SOLAR INSTALLATION MANUAL

17

JA SOLAR INSTALLATION MANUAL

Rated electrical characteristics such as Isc, Voc and Pmax are measured /- 3% of 

measurement uncertainty at Standard Test Conditions. Standard Test Conditions: 1000 W/m

2

 

Irradiance, 25°C Cell Temperature and 1.5 Air Mass.

Under normal conditions, photovoltaic Modules may produce higher current and/or voltage 

than reported at Standard Test Conditions. Accordingly, the values of short circuit current, 

Isc, and open circuit voltage, Voc, marked on Modules should be multiplied by a factor of 

1.25 when determining component voltage ratings, conductor capacities, fusing sizes, and 

size of controls connected to the Modules output. 

Voltages are additive when Modules are connected directly in series, and Modules currents 

are additive when Modules are connected directly in parallel, as illustrated in Figure 5.

Modules with different electrical characteristics must not be connected directly in series.

6. ELECTRICAL INSTALLATION

6.1 Electrical Property

Series wiring and Parallel wiring

Series wiring

Parallel wiring

Figure5: 

Electrical diagrams of series and parallel wiring

Over-current 
protection devices

Connector

Diodes

The  maximum  number  of  Modules  that  can  be  connected  in  a series  string  must be 

calculated  in accordance  with applicable regulations in  such  a  way  that  the  specified 

maximum system voltage (The maximum system voltage of JA Solar Modules is DC 1000V 

according to the safety appraisal of the IEC61730) of the Modules and all other electrical 

DC components will not be exceeded in open-circuit operation at the lowest temperature 

expected at the PV system location.

Correction factor for the  open-circuit voltage  can be calculated based on the following 

formula: C

Voc

=1-

β

Voc

×(25-T). T is the lowest expected ambient temperature at the system 

location. 

β

(%/

)  is  the  temperature  coefficient  of the selected  module  Voc  (Refer  to 

corresponding datasheet). 

An appropriately rated  over-current  protection device must be used  when the reverse 

current could exceed the value of the maximum fuse rating of the Modules. An over-current 

protection device is required for  each  series string if  more  than two series strings are 

connected in parallel

These junction boxes have been designed to be easily interconnected in series for their 

well-connected cable and the connector with IP67 protection grade. Each Modules has 

two single-conductor wires, one positive and one negative, which  are pre-wired  inside 

the junction box. The connectors at the  opposite end of these wires allow  easy series 

connection of adjacent Modules by firmly inserting the positive connector of a Module into 

the negative connector of an adjacent Module until the connector is fully seated.

Use  field  wiring  with  suitable  cross-sectional  areas  that  are  approved  for  use  at  the 

maximum short-circuit current of the Modules. JA Solar recommends installers use only 

sunlight resistant cables qualified for direct current (DC) wiring in PV systems. The minimum 

wire size should be 4mm2.

Rating Required Minimum Field Wiring

6.2 Cables and Wiring

Testing Standard

Wire size

Temperature Rating

TÜV 2 PfG 11694

4mm2

-40ºC to +90ºC

ELECTRICAL INSTALLATION

ELECTRICAL INSTALLATION

Содержание JAM5 Series

Страница 1: ...ference and in case of sale or disposal of the Modules For any questions please contact our Global Quality and Customer Service department for further information www jasolar com JA SOLAR INSTALLATION...

Страница 2: ...1 Conventional Requirements 10 5 2 Installation Methods 11 6 ELECTRICAL INSTALLATION 16 6 1 Electrical Property 16 6 2 Cables and Wiring 17 6 3 Connectors 18 6 4 Bypass Diodes 18 7 GROUNDING 19 7 1 Gr...

Страница 3: ...product specifications or installation manual without prior notice Failure to comply with the requirements listed in this manual will invalidate the Limited Warranty for Modules as provided by JA Sol...

Страница 4: ...ooftop that is capable of handling the additional weighted load of PV system components including Modules by a certified building specialist or engineer and have a formal structure of the complete ana...

Страница 5: ...les top surface To avoid damage to the backsheet do not scratch or hit the backsheet Do not drill holes in the frame This may compromise the frame strength and cause corrosion of the frame Do not scra...

Страница 6: ...of lightning strikes Do not use Modules near equipment or in locations where flammable gasses may be generated or collected 4 INSTALLATION CONDITION 4 1 Installation Position and Working Environment...

Страница 7: ...ny roof penetration required to mount the Modules must be properly sealed to prevent leaks Observe the linear thermal expansion of the Modules frames the recommended minimum distance between two Modul...

Страница 8: ...d on a supporting structure rail by metal clamps It is recommended to use the clamps under the following condition or approved by system installation Size No less than 38mm width Thickness No less tha...

Страница 9: ...the installation in extreme environment the maximum static load on the back of the Modules is 2400 Pa i e wind load and the maximum static load on the front of the Modules is 5400 Pa i e wind and snow...

Страница 10: ...d all other electrical DC components will not be exceeded in open circuit operation at the lowest temperature expected at the PV system location Correction factor for the open circuit voltage can be c...

Страница 11: ...e of 12 AWG can be used as grounding clamp The copper wire should not be compressed during the installation 7 GROUNDING JA Solar Modules use an anodic oxidized aluminum frame to resist corrosion So th...

Страница 12: ...ire The materiel and size of grounding wire should meet the relevant requirements of the national regional and local rule law and standard D Finish the mounting with tightening the binding bolt of the...

Страница 13: ...Modules such as other Modules system support bird drops and a lot of dust clay or plant and so on these may distinctly reduce the power output JA Solar advises that there should be no obstructed objec...

Страница 14: ...BK 54 SI 240 34 45 28 28 8 99 8 49 16 34 1000 15 0 049 0 34 0 43 1482 991 40 30 17 235 34 29 28 09 8 86 8 37 16 00 230 34 13 27 90 8 73 8 24 15 66 225 33 97 27 71 8 60 8 12 15 32 220 33 74 27 41 8 43...

Страница 15: ...0 1000 15 0 062 0 33 0 45 1630 980 35 28 1650 991 40 30 18 4 18 5 255 37 85 30 80 8 84 8 28 15 59 250 37 65 30 49 8 78 8 20 15 29 245 37 43 30 17 8 72 8 12 14 98 240 37 32 29 93 8 63 8 02 14 68 235 37...

Страница 16: ...1000 15 0 062 0 33 0 45 1956 991 45 35 22 5 305 46 20 36 97 8 60 8 25 15 73 300 46 08 36 82 8 53 8 15 15 48 295 45 90 36 60 8 48 8 06 15 22 290 45 72 36 39 8 42 7 97 14 96 285 45 41 36 08 8 38 7 90 14...

Страница 17: ...ign Size of Modules Overall Dimension 1580 808 40 30mm Overall Dimension 1580 1062 40 30mm Overall Dimension 1650 991 40 30mm Overall Dimension 1956 991 45 35mm Overall Dimension 1482 991 40 30mm Over...

Отзывы: