background image

User manual  

AKKU

TEC

 2412 VdS 

 

Document 

 

page 2 / 16 

0812G01B02-160422.docx 

 

 

 

 

1.  General 

The accumulator buffered DC supply guarantees a safe backup of the DC supply in case of a mains failure. 
Every other use is strictly excluded. 
The operating instructions must be read prior to use or installation; all instructions have to be considered! 
Commissioning and maintenance may only be performed by qualified specialist personnel. 
All warranty and guarantee claims could be lost in case of non-observance or unauthorised modifications! 
This power supply is only a built-in unit with VdS certification. For a proper VdS installation the external power 
supply must be installed in a housing with protective system IP30 or better. Furthermore the temperature sen-
sor which is optionally available must be installed for temperature tracking 

1.1 

General safety notes 

 

NOTE 

The operating instructions must be read prior to installation or use of the unit. The instructions 
must be observed. All warranty claims could be lost in case of non-observance!

 

 

DANGER 

Only specialised electricians are authorized to commission and maintain the unit. Improper han-
dling with voltage procedures or lead accumulators can lead to electric shock and severe burns.

 

 

DANGER 

All work on the unit may only be performed in de-energized state!  
The five safety rules must be observed. 
Input and output lines must be sufficiently dimensioned and fused! 
Never open the housing. Repair may only be done by the manufacturer! 
Non-observance can lead to fatal electric shocks. 

 

CAUTION 

For use in a controlled environment refer to chapter 11 Technical Data for environmental condi-
tions.

 

 

NOTE 

In case of malfunction we recommend to send the unit to the manufacturer

 

The unit has been developed for protection class I and has the degree of protection IP20. Operation is only 
admissible in dry rooms. The operation is only allowed in closed housings. This device is designed for pollu-
tion degree 2. The applicable VDE regulations, in particular VDE 0100 and EN 60204, must be observed!  
The admissible ambient temperature range must be observed! 
The DC output circuit must be fused externally in order to avoid overload! (See section 3.2) 
The two energy sources (mains and lead accumulator) must be separated in order to de-energize the unit on 
the output side! 
Only the lead accumulator types specified for the unit must be used! The change of lead accumulators must 
only be performed when the unit is de-energized! (see section 7.2). If external buffer accumulators are used, 
accumulator safeguarding must be performed by the user! For safety reasons, the safeguarding element 
(overload and short circuit protection) must be arranged in close proximity to the accumulator set! If lead ac-
cumulators are used, sufficient air flow must be provided according to VDE 0510, part 2.  
Never interconnect new and used lead accumulators, or lead accumulators of different types or from different 
manufacturers. 
Used lead accumulators must be disposed carefully. 
 

 

Содержание AKKUTEC 2412 VdS

Страница 1: ...1 Installation 3 2 Connection 3 3 Connection lead accumulator 3 4 Connection of mains voltage 3 5 Connection load 3 6 Signal contacts 3 7 Circuit diagram 4 Start Up 9 4 1 Display and messages 5 Operation 9 5 1 Mains operation 5 2 Back up operation 5 3 Deep discharge protection 5 4 Accumulator circuit monitoring 5 5 Accumulator test 5 6 Temperature tracking optional 5 7 Shut Down 5 8 Acoustic alarm...

Страница 2: ...imensioned and fused Never open the housing Repair may only be done by the manufacturer Non observance can lead to fatal electric shocks CAUTION For use in a controlled environment refer to chapter 11 Technical Data for environmental condi tions NOTE In case of malfunction we recommend to send the unit to the manufacturer The unit has been developed for protection class I and has the degree of pro...

Страница 3: ... observed see section 11 Technical Data The units must be pro tected against humidity and direct sunlight If lead accumulators are included they must be recharged at least each half year in case of longer storage 3 Installation and connection 3 1 Installation The unit must be installed in a way that the necessary cooling is guaranteed A minimum distance of 75mm must be kept to neighbouring units o...

Страница 4: ...t and the lead accumulator current The DC output circuit must be fused externally in order to avoid overload If the external power supply is installed as a part of a fire alarm system the following regulations must be ob served in their currently valid version DIN 14675 Fire detection and alarm systems design and operation DIN VDE 0833 part 1 2 Alarm systems for fire intrusion and hold up DIN VDE ...

Страница 5: ... must be provided according to VDE 0510 part 2 NOTE Only use VdS approved lead accumulators Never use different lead accumulator types nor lead accumulators of different manufacturers nor old and new accumulators together CAUTION Protect i e insulate the poles when connecting lead accumulators In case of short circuits there is the danger of severe burns by arcs or hot parts CAUTION Hydrogen is ge...

Страница 6: ...osed of the maximum charge rectifier cur rent and the lead accumulator current The DC output circuit must be fused externally in order to avoid overload 3 6 Signal contacts The status of the external energy supply can be forwarded to a superior central unit via signal contacts The relay contacts are linked to the LED s with the same name Thus the illumination of an LED effects the corresponding re...

Страница 7: ...g Fault Netz Mains OK Bat OK IO 2 Current Share CS Temp Sensor 1 2 3 4 5 6 7 COM1 TxD RxD 2 3 5 RS232 µP Ua Control Shut Down Netz Mains OK 4 5 6 7 8 9 1 2 3 Bat OK Störung Fault Batt Sync Eingang Input Master Slave Mains Master Slave DC Output Accumulator connection 30V DC 0 5A 30V DC 0 5A 30V DC 0 5A AKKUTEC 2412 VdS ...

Страница 8: ...on Terminal UA1 UA1 UA10 UA10 Output terminals 1 10 Fuse F1 F10 Ubat Ubat Accumulator terminal Temp Temperature sensor Remark With the new generation of the fuse board NBP21248G10001 only one type exists For extension however an equal fuse board is used Kunden anschluß Netz N PE PE L1 Kundenanschluß Kundenanschluß Kundenanschluß L 1 N BE PSU12 CF IO 2 Betrieb Operation Bat OK Störung Fault Netz Ma...

Страница 9: ...rval 1 min if the lead accumulators are reverse poled if the Ri accumulator internal resistance is too high test interval 10 min Error LED yellow illuminates at back up operation if the accumulator circuit is interrupted if the lead accumulator is reverse poled if the accumulator internal resistance is too high in case of a fuse blow on the fuse board if activated The LED s are coupled to the sign...

Страница 10: ...for special requirements Special characteristics Voltage current temperature monitoring adaptation of internal re sistance threshold for different lead accumulator sizes activation deactivation for external fuse board 5 6 Temperature tracking optional Lead accumulators have a temperature coefficient of approximately 3 mV per C and per cell For the usage without temperature sensor the final chargin...

Страница 11: ...ng measurement of the internal resistance of the accumulator Master IO 2 6 to Slave IO 2 6 The CS Current Share Bus is used to share the load between both power supplies A lack of this signal results in the overload of the Master unit Master IO 2 5 to Slave IO 2 5 The signal contact mains operation is at both power supplies active They must be connected in se ries to detect a mains failure of both...

Страница 12: ...elivered from the factory are preset as Master Complete switch cabinets with Master Slave configuration are adjusted correctly in the factory If a Slave must be replaced the replacement unit must be adjusted as Slave Configuration for Slave operation The unit must be completely switched off On the upper side of the unit a double dip switch can be seen through the grid Press the dip with the indica...

Страница 13: ...ehler Verweisquelle konnte nicht ge funden werden Remove electrical connections from the lead accumulators 2 Pol CombiCon Ubat Loosen the accumulator bracket retain lead accumulator at the same time Remove lead accumulators Installation of lead accumulators The installation is performed as described above only in reverse order Take care to ensure correct polarity In case of a reverse polarity of t...

Страница 14: ...So the materials are separated and recycled ac cording to their characteristics This is a big contribution to protecting the environment NOTE Used lead accumulators must be disposed of properly 10 Norms and regulations Power supplies for fire alarm systems are subject to rigorous regulations the power supply unit of the fire alarm system is tested according to the European Product Standards EN 54 ...

Страница 15: ...iciency 89 Ue 230 V Ua 26 4 V DC Ia INenn Voltage ripple 150 mV eff Internal device protection 2 5 A T 250 V Fuse DC output circuit external 15 A T UL 248 Fuse DC Battery circuit external 15 A T UL 248 Connection in parallel Yes Connection in series Yes Max signal contact load Mains OK 1 30 V 0 5 A potential free relay contact Max signal contact load Bat OK 1 30 V 0 5 A potential free relay contac...

Страница 16: ...Q33G3M01 Temperature sensor MTIAQ33G3M04 Temperature sensor MTIAQ33G3M05 Every fuse output is monitored separately If a fuse blows the corresponding LED goes out A blown fuse is notified to the AkkuTEC or the PLS with collective massage Fuse board NBP1248G10001 Decoupling diode set including a double Schottky diode on a potential free cooler wiht cover against direct touch and top hat rail clamb K...

Отзывы: