Quick Start Guide J4C S20-S300 

 

actuatedvalvesupplies.com

 

Actuated Valves Supplies Ltd

 

                                      

Tel: +44(0)3300535750 

 

Overview 

 

 

 

 

140-300 

Version: 

 

20-35-55-85 

 

 

 
 

A  Manual Override Switch 

 

B  Handwheel 

 

C Dome indicator 

 

 

 

 

 

 

 

   

 

 

D Status LED 

   

 

 

 

 

 

 

 

   

E Wiring Diagram 

   

 

 

 

 

   

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F Nameplate 

   

 

 

 

 

   

   

 

   

 

 

 

   

   

   

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

   

 

 

 

 

Model Comparison: 

   

 

 

  

   

 

   

   

Duty 

Operating Temp. 

 

  Heater Power         Ingress (IEC60529) 

2x End of Travel Sw. 

Rating= 75% 

   

-20°C - +70°C 

 

3.5 W 

 

 

 

IP67 

 

SPST NO 5A 125VAC / 3A 250VAC 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Specific: 

   

   

 

 

   

   

Optional 0,1A 30VDC (See Page 1) 

   

 

 

 

 

   

   

 

 

 

 

 

 

   

 

Current consumption at max. torque 

 

 

 

Runtime 

 

 

 

 

 

 

Working / 

 

  Without Load 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modell 

24V AC 

 

24V DC 

 

110V AC 

230V AC 

Break Torque 

s/90° ±10% 

Weight 

S 20 

 

1.3A / 30.7W 

 

1.0A / 23.4W 

0.3A / 32.7W 

0.2A / 46W 

 

20Nm / 25Nm 

 

10s (5.5s) 

1.8kg 

S 35 

 

1.7A / 40.2W 

 

1.4A / 32.8W 

0.4A / 41.9W 

0.2A / 46W 

 

35Nm / 38Nm 

 

10s 

1.9kg 

S 55 

 

2.0A / 47.5W 

 

1.6A / 39.0W 

0.4A / 47.0W 

0.2A / 46W 

 

55Nm / 60Nm 

 

13s 

2.4kg 

S 85 

 

1.5A / 36.0W 

 

1.2A / 29.3W 

0.3A / 36.5W 

0.2A / 46W 

 

85Nm / 90Nm 

 

29s 

3.0kg 

S140 

 

3.3A / 79.2W 

 

2.5A / 60.7W 

0.7A / 78.7W 

0.4A / 105.6W 

 

140Nm / 170Nm 

 

25s 

5.2kg 

S300 

 

3.3A / 79.2W 

 

2.7A / 64.7W 

0.8A / 84.7W 

0.5A / 113.5W 

 

300Nm / 350Nm 

 

48s 

5.2kg 

Operation

 

     

   

 

 

  

   

 

   

   

Status Light (D) 

   

   

 

 

  

   

 

   

   

 

 

Operating Status 

   

 

 

   

 

LED Flash Sequence 

   

 

No power supply 

 

Unit is in open position 

 

Unit is in closed position 

 

Unit is in stop position 

 

Unit is moving to open position 

 

Unit is moving to closed position 

 

Torque protection stopped move to open 

 

Torque protection stopped move to closed 

 

Manual Override Engaged 

 

Manual override (A/B) 

 

All J4C models have a manual emergency override for manual operation in the event of a power failure. To activate the 
manual override, the "AUTO-MAN" switch (A) must set to "MAN", this declutches the engine from the transmission. 

 

Once in manual you can turn the drive with the handwheel (B). 
 

 

After about four times the expected actuation time, the engine is automatically stopped by the electronics. 

 

 
If the drive is to be put back into autonomous operation, switch the switch (A) back to the "AUTO" position and the motor will be 
coupled again. 
 

 

If the motor has switched off automatically, it can be reactivated either by driving in the other direction or by power cycling 
the device. 
 

 

The change-over switch must not be over-tightened. 

 

If the switching is difficult, the gear can be synchronized by means of a handwheel. The screw of the 
switch must never be loosened! 

 