36
11. Maintenance of the exchanger and fans
Inspect the exchanger and the fans once every four years
• Remove Perilex plug
(A)
from the socket.
• Detach the front by removing screws
(B)
.
• Detach plugs
(C)
(only with bypass).
• Remove rubber seal
(D)
.
• Pull band
(E)
to remove the heat exchanger and the drip tray
(F)
.
Remove the heat exchanger from the drip tray
(F)
.
• If necessary, clean the exchanger. Immerse the exchanger several
times in warm water (max. 40°C), containing a solution of non-aggres-
sive dishwasher detergent. Immerse the exchanger with the ribbed side
vertical. Then rinse the exchanger with clean, warm water (max. 40°C).
Hold the exchanger by the green side panels and shake the water out
of the exchanger.
☞
Do not use aggressive or dissolvent detergents in cleaning.
• Use a soft brush to clean the fan blades.
• Use a vacuum cleaner to remove any dust.
☞
Take care not to damage the fan blades.
☞
Take care not to damage the temperature sensor
(H)
.
• Close covers, replace exchanger and drip tray, fit the rubber seal,
connect plugs, attach front and insert Perilex plug into socket.
☞
When fitting the exchanger and the drip tray ensure the condensa-
tion drain is on the same side as the condensation drain connection.
11a.
11b.
11c.
11d.