GENERAL INFORMATION

An 

Ultra Violet Disinfection System

 is a versatile unit designed to kill waterborne bacteria using the proven

method of exposure to ultra violet light.

The unit is made from a tubular quartz sleeve in which a UV lamp is inserted. Both components are housed in a
stainless steel outer chamber called a reactor. Water is disinfected as it passes through the reactor and is exposed
to a high intensive UV light that penetrates and deactivates bacterial cells.

The outer of bacteria and viruses differ in thickness and it is this thickness of skin which determines the amount of
UV light exposure to prevent their reproduction, rendering them dead.

UV systems should be installed with pre-filtration down to 5 micron. This prevents an effect called shadowing
where micro-organisms could hide behind particles in the water.

LOCATION

The  steriliser  should  be  mounted  in  a  location
allowing  sufficient  room  at  the  end  of  the  unit  to
withdraw the lamp and quartz sleeve. If this is not
possible use a flexible hose set allowing the chamber
to  be  unclipped  from  it’s  mounting  bracket(s)  for
service and lamp change. Where possible the unit
should be installed to treat all the water as it enters
the  system.  If  treated  water  is  to  be  stored,  the
storage tank should be fitted with a close fitting  lid
and the overflow protected with a fly screen (Water
by-law 30). Tanks should only hold sufficient water for
a few hours use.

LAMP LIFE

The lamp will continue to emit sufficient ultra violet
for efficient operation of the unit for a period of
4,000 hours. The lamp must always be replaced at
this  interval  although  a  safer  recommendation
usage period is one year or 2,000 hours. Failure to
change  the  lamp  will  result  in  insufficient  UV
dosage for bacteria killing.

ELECTRICAL INSTALLATION

All  metal  components  should  be  earth  bonded.
Ensure the earth wire from the power supply is
connected to the earth point located at the one end
of the chamber. To avoid possible electric shock,
special care should be taken since water is present
near electrical equipment.

PLUMBING INSTALLATION

Although  the  chamber  can  be  mounted  at  any
angle,  the  outlet  connection  should  always  be
uppermost to prevent airlocks in the chamber - the
ideal  installation  is  vertical.  Good  quality  pre
filtration is essential for correct operation. Replace
filters as required and always fit new elements,
never wash a dirty filter.

QUARTZ SLEEVE

The quartz sleeve should be checked and cleaned
periodically.  When  cleaning  the  quartz  sleeve
ensure the unit is isolated from the electrical supply
and check the water supply is also turned off prior
to servicing.

www.jdultrasonics.co.uk    

  +44 (0)1924 378 448

UV DISINFECTION - OPERATING & MAINTENANCE

Never operate the unit if the lamp is outside the chamber.

Never stare at the light source.

Exposure to ultra violet light can cause conjunctivitis and erythema.

Содержание sonicom ATLAS

Страница 1: ...sonicom J D UltraSonics ULTRASONIC NOZZLES AIR ATOMISERS DUST SUPPRESSION HUMIDIFICATION ATOMISING FOGGING ATLAS ULTRA VIOLET DISINFECTION UNIT OPERATING AND MAINTENANCE ...

Страница 2: ...low protected with a fly screen Water by law 30 Tanks should only hold sufficient water for a few hours use LAMP LIFE The lamp will continue to emit sufficient ultra violet for efficient operation of the unit for a period of 4 000 hours The lamp must always be replaced at this interval although a safer recommendation usage period is one year or 2 000 hours Failure to change the lamp will result in...

Страница 3: ...nd on the top end of the lamp Fit the new lamp into the connector by holding the ceramic end and noting the keyed format which ensures correct connection www jdultrasonics co uk 44 0 1924 378 448 UV DISINFECTION OPERATING MAINTENANCE OPERATING AND MAINTENANCE INSTRUCTIONS Caution Prior to performing any work on the disinfection system always disconnect the power supply first To replace the lamp it...

Страница 4: ...hanging the lamp on the system the controller must be reset in order for the system to begin its countdown function on a newly installed lamp To perform this reset firmly depress the button on the front of the controller and then manually power up the unit Keep holding down the button for five seconds until the controller has reset the internal timer Release the button and the lamp countdown featu...

Отзывы: