TROUBLESHOOTING

Diagnostic LEDs

The controller has 4 LED indicators. These indicators can aid in troubleshooting equipment operation problems. The 
following table lists the functions of the controller’s LEDs in the order they appear from left to right on the unit.

Figure 3: Terminal Unit Controller Controller LEDs

Service (SRV)

Status (RUN)

Network (WNK)

Fault (FLT)

Troubleshooting Tips

The following table provides tips on resolving common issues.

LED Indication

Status

– Solid green when running and configured by an LCI
– Flashing green when running and NOT configured by an LCI

Network

– Yellow while the controller is transmitting data onto the FTT-10A network 
– Green when there is network activity
– Off when there is no network activity

Fault

– Solid red when a fault condition exists

Service 

– Illuminated when the service pin is pushed

Problem

Solution

Controller is not running and Status 
LED is not illuminated.

No power to controller. Verify the voltage on the controller’s power connector (24 VAC). 

How do I reset the controller?

The controller can be reset by the LCI, or you can cycle power to the controller. Refer to 
the LCI documentation for more information on resetting the controller using the LCI.

I am using a TS303 thermostat and 
cannot force the fan ON.

On the VAV Series controller, the Fan Override button is disabled. Model TS303 is not 
recommended for use with VAV Series controllers.

On other iWorx® controllers, the sta-
tus LED will turn Red when the con-
troller has entered a fault mode that 
requires a reset. Are there any such 
modes on the VAV Series?

Yes, but it doesn't require a reset. As with any of the controllers, if the controller detects 
that no TS300 series sensor is present, an alarm is issued, the controller enters fault 
mode, and the LED is turned red. However, this type of failure doesn't require a manual 
reset.

Can VAV Series controllers have 
independent schedules?

Yes, each VAV Series controller on the network can be part of a different LCI group con-
taining a different schedule. Remember the LCI is limited to 16 groups and 16 sched-
ules.

Содержание VAV Series

Страница 1: ...n Instructions 4 Precautions 4 General 4 Static Electricity 4 Location 4 FCC Compliance 4 Before Installing 5 About this Document 5 Inspecting the Equipment 5 What is Not Included with this Equipment...

Страница 2: ...ints for occupied unoccupied heating Networked operation using LONWORKS Technology Thermostat with space temperature setpoint adjust occupancy override Integrates with Multiplex Package Unit controlle...

Страница 3: ...VPU2 Application Guide Document No 505 010 Application Engineers Installers Service Personnel Start up Technicians End user Provides instructions for setting up and using the iWorx VPU controller iWo...

Страница 4: ...y or as required by National Electrical Code the unit is intended to be installed within an electrical control enclosure Operate where ambient temperatures do not exceed 122 F 50 C or fall below 32 F...

Страница 5: ...anges specified for this equipment The equipment must be installed within 500 feet of all input peripherals smoke detectors sensors etc that will be connected to the equipment Selecting a Power Source...

Страница 6: ...g tab at the left of the controller 6 Drive the mounting screw through the hole in the mounting tab and into the metal of the damper box 7 Set the motor stops to prevent the actuator motor from over d...

Страница 7: ...011 Taco Electronic Solutions Inc Figure 1 Mounting Dimensions Routing Cabling to the Device Cabling used to connect the power source and cabling used to connect the FTT 10A network must remain separa...

Страница 8: ...ct the power source to earth ground WIRING INFORMATION WARNING Terminals 9 14 17 and 20 are connected internally on all Terminal Unit Controller controllers Disconnect ALL power sources when installin...

Страница 9: ...acent common on T3 See Figure 2 for details Fan Start Stop FAN The fan outputs must be connected to a 24 VAC pilot relay with EMF protection Connect the Fan to T7 and the adja cent common on T6 See Fi...

Страница 10: ...minal 100VA max requires an external class 2 supply Power Consumption 15VA with no external loads maximum limited by the class 2 supply rating Recommended Sensor Wire FTT 10A Network Speed 78KBPS Cabl...

Страница 11: ...Processor 3150 Neuron 10 MHz Flash 48 Kilobytes SRAM 8 Kilobytes Termination 0 197 5 0 mm Pluggable Terminal Blocks 14 22 AWG Actuator Angle of rotation 95 adjustable Torque 35 in lb 4 Nm nominal Env...

Страница 12: ...D is not illuminated No power to controller Verify the voltage on the controller s power connector 24 VAC How do I reset the controller The controller can be reset by the LCI or you can cycle power to...

Страница 13: ...AV box damper Yes using the LCI there is a mode that an air balancer can manipulate the damper or set it to maintain a specified flow My VAV Series boxes are not enter ing heating or cooling mode Have...

Страница 14: ...iWorx VAV Series 14 502 011 Effective March 16 2011 2011 Taco Electronic Solutions Inc...

Страница 15: ...iWorx VAV Series 502 011 Effective March 16 2011 15 2011 Taco Electronic Solutions Inc...

Страница 16: ...e covered by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any oth...

Отзывы: