12KHR-N
3 – 2
9
AC overcurrent
error
Operating frequency lowers if out-
door AC current exceeds peak
control current value. outdoor
stops if compressor AC current
exceeds peak control current
value at minimum frequency.
When compressor is
in operation
Operation OFF or ON
Yes
✩
1
Yes
Yes
10
AC overcurrent
error in compressor
OFF status
Indoor and outdoor units stop if
outdoor AC current exceeds
about 3 A while compressor is in
non-operation status.
When compressor is
in non-operation
Replacement of
defective parts such
as IPM
Yes
✩
2
Yes
Yes
11
AC maximum cur-
rent error
Compressor stops if coutdoor AC
current exceeds 17 A.
When compressor is
in operation
Operation OFF or ON
Yes
✩
1
Yes
Yes
12
AC current defi-
ciency error
Compressor stops if operating
frequency is 50 Hz or higher and
outdoor AC current is about 2.0 A
or lower.
When compressor is
in operation
Operation OFF or ON
Yes
✩
1
Yes
Yes
13
Thermistor installa-
tion error or 4-way
valve error
Compressor stops if high and low
values of temperatures detected
by outdoor unit heat exchanger
thermistor (TH2) and 2-way valve
thermistor (TH5) do not match
operating cycle.
3 minutes after com-
pressor startup
Operation OFF or ON
Yes
✩
1
Yes
Yes
14
Compressor high
temperature error
Compressor stops if compressor
chamber thermistor (TH1)
exceeds about 114
q
C, or if there
is short-circuit in TH1.
When in operation
Operation OFF or ON
Yes
✩
1
Yes
Yes
15
Outdoor unit heat
exchanger ther-
mistor short-circuit
error
Compressor stops if there is
short-circuit in outdoor unit heat
exchanger thermistor (TH2).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
16
Outdoor unit outside
air temperature
thermistor short-cir-
cuit error
Compressor stops if there is
short-circuit in outdoor unit out-
side air temperature thermistor
(TH3).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
17
Outdoor unit suction
thermistor short-cir-
cuit error
Compressor stops if there is
short-circuit in outdoor unit suc-
tion thermistor (TH4).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
18
Outdoor unit 2-way
valve thermistor
short-circuit error
Compressor stops if there is
short-circuit in outdoor unit 2-way
valve thermistor (TH5).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
19
Outdoor unit heat
exchanger ther-
mistor open-circuit
error
Compressor stops if there is
open-circuit in outdoor unit heat
exchanger thermistor (TH2).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
20
Outdoor unit outside
air temperature
thermistor open-cir-
cuit error
Compressor stops if there is
open-circuit in outdoor unit out-
side air temperature thermistor
(TH3).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
21
Outdoor unit suction
thermistor open-cir-
cuit error
Compressor stops if there is
open-circuit in outdoor unit suc-
tion thermistor (TH4).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
22
Outdoor unit 2-way
valve thermistor
open-circuit error
Compressor stops if there is
open-circuit in outdoor unit 2-way
valve thermistor (TH5).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
23
Outdoor unit dis-
charge thermistor
open-circuit error
Compressor stops if there is
open-circuit in outdoor unit dis-
charge thermistor (TH1).
At compressor star-
tup
Operation OFF or ON
Yes
✩
1
Yes
Yes
24
Serial signal error
Compressor stops if outdoor unit
cannot receive serial signal from
indoor unit for 30 seconds.
When in operation
Reset after reception
of serial signal
None
None
None
25
Compressor star-
tup error
Compressor stops if compressor
fails to start up.
At compressor star-
tup
Operation OFF or ON
Yes
✩
3
Yes
Yes
Function
Operation
Self-diagnosis
result display
Description
Detection period
Reset condition
Indoor
unit
error
display
Indoor
unit
Outdoor
unit