Installation instructions

Installation and hydraulic connections (Fig. 5)

Prepare a recess in the wall having the correct size (refer to Fig. 1)

(a) 

Position 

EQUICOMPACT

 into the centre of the recess

(b) 

Remove the heating unit insulation (if provided)

(c) 

Connect return piping both to the primary and to the secondary side of the heating unit

(d) 

Connect flow piping both to the primary and to the secondary side of the heating unit

Warning

. The contact with high-temperature fluid can cause even serious scalding. Use the adequate personal protection equipment (PPE).

(e) 

Open the four (two red and two blue) heating unit shut-off valves

(f) 

Remove the plug from the static balancing valve by means of an 8-mm Allen key

(g) 

Drive the valve fully open, making sure that the incision is parallel to the flow direction

(h) 

Wash the plant

(i) 

Close the red shut-off valves of the heating unit

(j) 

By means of an 8-mm Allen key, remove the plug sealing the strainer housing. Remove the strainer cartridge, wash it carefully, the put 

it back into the housing. Put the plug back and tighten it.

Installation of meters (Fig. 6)

(a) 

Close the shut-off valves of the heating unit

(b) 

Loosen the nuts at the endpoints of the template, then remove it. Position two new gaskets and the heat meter instead of the template, 

then tighten the nuts without forcing too much

Warning

. Pay extreme attention to flow direction. A wrong installation of the heat meter precludes the correct metering and may damage the device.

(c) 

By means of a 15-mm wrench, unscrew and remove the plug from the sensor pocket (3 in Fig. 3) and insert the heat meter flow sensor 

by following the instructions provided by the manufacturer of the device 

(d) 

Seal the meter and the flow sensor

The following steps must be carried out only if the application requires the installation of one or more volumetric meters, and should be repeated for 

each domestic line.

(e) 

After checking that both the shut-off valves of the domestic line are closed, loosen the nuts at the endpoints of the template, then 

remove it. Position two new gaskets and the water meter instead of the template, then tighten the nuts without forcing too much

(f) 

Seal the meter.

Commissioning (Fig. 7)

According to the designer specifications, make the static balancing of the user plant by following these steps:

(a) 

Open the heating unit shut-off valves

(b) 

Slowly adjust the balancing selector position until the design flow rate is showed by the heat meter display 

Warning

. If the installation is to be equipped with dynamic balancing devices, either flow stabilising valves or differential pressure controlling valves can 

be installed outside 

EQUICOMPACT

 unit. In case of differential pressure control valve for return mounting, a dedicated pocket (5 in Fig. 3) can be used 

for the connection of the high-pressure capillary probe. The connection thread is soft-seal M10x1.

(c) 

Once the adjustment has been completed, put back the plug

(d) 

Seal the valve using of the proper holes

(e) 

Open all the shut off valves, both on heating and domestic lines

(f) 

Put back the insulation shell (if provided).

In case of plastering-ready door, plaster the door aside. Complete the necessary masonry operations, then put back the plastered door once the work 

is over.

Other accessories

Zone valve 4 in Fig. 3 can be controlled by an actuator wired to a room thermostat. IVAR offers normally closed electro-thermal heads cod. 501508 

(230 V) or cod. 501524 (24 V) together with chrono-thermostat cod. 580012 (heating only) or cod. 580015 (heating/cooling). These components can 

be purchased separately.

Warning

. Follow the dedicated instructions of the electronic devices for their correct installation. In particular, if normally-closed electro-thermal heads 

with “first open” function are installed (see cod. 501508 or cod. 501524), please consider that such devices are delivered in open state. This function 

is permanently disengaged after the first 6 min of powered use at the working voltage. Once the initial cycle has been completed, the head will be 

regularly open when powered, and closed otherwise.

5

300451-04-17

Содержание EQUICOMPACT

Страница 1: ...300451 04 17 Manuale di istruzioni Instruction manual EQUICOMPACT ...

Страница 2: ...solamenti singoli Ingombri in Fig 1 Descrizione I moduli di utenza sono gruppi polifunzionali che riuniscono in un solo punto i dispositivi di contabilizzazione diretta e valvole di controllo EQUICOMPACT è una soluzione versatile e dall ingombro ridotto per la gestione del calore La sua caratteristica valvola di zona a due vie lo rende adatto all utilizzo con pompe a portata variabile questo binom...

Страница 3: ...iuse allentare i dadi agli estremi del tronchetto DIMA e rimuoverlo Posizionare le guarnizioni inserire il contatore volumetrico al posto del distanziale e serrare i dadi senza forzare f Piombare il contatore Messa in opera Fig 7 Secondo le modalità previste dal progettista effettuare il bilanciamento idraulico statico dell utenza procedendo come segue a Aprire le valvole di intercettazione del bl...

Страница 4: ...sed shell does not require the addition of individual insulation shells Dimensions in Fig 1 Description User modules are multi functional groups combining metering devices and control valves in a single unit EQUICOMPACT is a flexible small footprint solution for heating management Its characteristics two way zone valve makes it suitable to the application with variable speed pumps this combination...

Страница 5: ...lves of the domestic line are closed loosen the nuts at the endpoints of the template then remove it Position two new gaskets and the water meter instead of the template then tighten the nuts without forcing too much f Seal the meter Commissioning Fig 7 According to the designer specifications make the static balancing of the user plant by following these steps a Open the heating unit shut off val...

Страница 6: ...03 98 230 80 115 70 130 G 1 G M10X1 M30X1 5 506576S EQCP25 230 80 70 130 G 1 G M10X1 M30X1 5 ART COD A B C D E F G H L M AC 860B 200199 510 510 444 444 450 450 130 80 110 36 AC 860L 200299 520 520 442 442 450 450 130 80 110 36 ART COD A B C D E F G H L M AC 860IB 506665B 530 530 400 400 470 470 130 80 92 43 Fig 1 7 6 4 3 2 8 5 1 9 Fig 3 Fig 2 C A B 6 300451 04 17 ...

Страница 7: ...Fig 4 a b c Fig 5 a d g j b e h c f i 7 300451 04 17 ...

Страница 8: ...que momento e senza preavviso Tutti i diritti sono riservati La riproduzione completa o parziale è vietata senza il previo consenso del proprietario del copyright I V A R S p A reserves the right to make enhancements and changes to products and relative documentation at any time without prior notice All rights reserved Reproduction even partial is forbidden without prior permission by the copyrigh...

Отзывы: