background image

 

 

IAI3001D-01 

Page 6 of 8 

07/18 

B. Apply power to terminals marked 1 & 4 (CLOSE) 

 

The  actuator  will  drive  to  the  full  CLOSE  (CW)  position  (as  viewed  from  ABOVE  the 
actuator).

 

 

If this is NOT the correct stop position, refer to the “Limit Switch Setting” section in this 
manual to reset LS2.

 

Limit Switch Setting 

The travel cams are set to control the open and closed position of the valve. The position is set to stop the travel 
of the actuator when the travel cams activate the limit switch. Standard is two limit switches (LS1 & LS2), one 
for open, one for closed.  LS1 & LS2 limit the maximum range by disabling the electric motor. LS3 & LS4 are 
optional. See photo 8. They allow external equipment to confirm that the valve has reached the fully open and 
fully closed positions. 

Care must be taken to ensure that LS3 & LS4 are set to trip prior to LS1 & LS2 so that 

proper end of travel indication is provided.

 The travel cams can be adjusted with 2.5mm Allen key. 

 

 

To set LS1, the OPEN position (Full CCW Position):

 

o

 

Turn  power  off  and  use  manual  override 
to turn valve to the open position. 

 

o

 

Remove cover and loosen the set screw on 
the bottom cam, TC1.

 

o

 

Rotate cam clockwise to reset the switch 
contact.

 

o

 

Then,  slowly  rotate  cam  counter-
clockwise until a light click is heard.  

 

o

 

Securely tighten the cam and apply power 
to check the end position. 

 

 

To set LS2, the CLOSE position (Full CW Position):

 

o

 

Turn  power  off  and  use  manual  override 
to turn valve to the closed position. 

 

o

 

Loosen the set screw on cam TC2. 

 

o

 

Rotate cam counter-clockwise to reset the 
switch contact.

 

o

 

Then, slowly rotate cam clockwise until a 
light click is heard.  

 

o

 

Securely tighten the cam and apply power 
to check the end position. 

 

Photo 8

 

Содержание iVQ-E

Страница 1: ...Receiving Inspection Carefully inspect for shipping damage Damage to the shipping carton is usually a good indication that it has received rough handing Report all damage immediately to the freight carrier and your seller After unpacking the product and information packet please take care to save the shipping carton and any packing material in case of product return or replacement Verify that the ...

Страница 2: ...he actuators have been factory calibrated to operate between 0 and 90 Most quarter turn products will not require recalibration of these settings If any travel adjustment is necessary please refer to the Limit Switch Setting section below 2 The actuators are shipped in the full CLOSE CW position The 2 color mechanical position indicator shows CLOSE see Photo 2 and on the actuator base the referenc...

Страница 3: ...e maximum duty cycle as noted on the actuator nameplate Installation Notes These actuators are designed to be used between a horizontal and upright position Do NOT mount the assembly with the actuator top below a horizontal position When installing conduit use proper techniques for entry into the actuator It is preferred that the conduit entries face downward Use drip loops to prevent conduit cond...

Страница 4: ... Override A handwheel is supplied to be used as a manual override See Photo 4 If the handwheel is supplied with a rotating grip ensure that the nut on the bolt is threaded about 1 onto the bolt See photo 5 When the bolt is threaded into the handwheel the nut will prevent the bolt from being threaded further into the handwheel allowing the grip to rotate freely The handwheel does not require a clut...

Страница 5: ...n the jam nut By using a 17mm wrench and a 5mm Allen key loosen the jam nut Turn the stop set screw 7 turns CCW See Photo 7 Use the manual handwheel to move valve to full CLOSE CW position Screw in the stop screw until it bottoms out then turn back 1 turn While holding the stop screw secure with the 5mm Allen key tighten the jam nut Commissioning This procedure will assume that the actuator is ins...

Страница 6: ...closed positions Care must be taken to ensure that LS3 LS4 are set to trip prior to LS1 LS2 so that proper end of travel indication is provided The travel cams can be adjusted with 2 5mm Allen key To set LS1 the OPEN position Full CCW Position o Turn power off and use manual override to turn valve to the open position o Remove cover and loosen the set screw on the bottom cam TC1 o Rotate cam clock...

Страница 7: ...rox 3 o Securely tighten the cam and apply power to ensure that this switch trips before it reaches the end position To set LS4 CLOSE Auxiliary Switch o Ensure that the actuator is in the fully CW position o Loosen the set screw on cam TC4 o Rotate cam counter clockwise to reset the switch contact o Then slowly rotate cam clockwise until a light click is heard o Slowly continue to rotate in the sa...

Страница 8: ...nger than specified New valve may be required The voltage may be under over rated Check the supply voltage The actuator may be against one of the mechanical end stops Reset limit switches and adjust end stops again The valve does not move when given a signal or in manual operation Check installation between the actuator and valve as it may not be assembled properly Verify that the set screws of th...

Отзывы: