Page 16
Operation and Maintenance Instructions
THE NEW EcoHeater
DSEH180401.00.EN
Continuous product development may give rise to specification changes without notice.
4.3 Heat pump section, commissioning
Check list.
Check that the heat pump:
1. can communicate with sub-central unit, via COM or signal cable, with one
of the following operating options:
- External control: Signal for required heat
- Internal control: Signal temperature sensor supply line
- Tank charging: Signal temperature sensor accumulator tank
Internal control or tank charging can be used even in those cases when
the option for communication with the sub-central unit is lacking or not to
be used. The temperature sensor is then connected directly to the Eco-
Heater.
2. receives a signal from the temperature sensor for outdoor air (via COM or
signal cable)
3. - is connected with flexible hoses (particle filter on inlet, possible safety
valve at heat pump side)
- is vented to the highest point of the liquid
- has the liquid flow adjusted to value according to Technical data
4. has condensation outlet connected to floor drain/sewer (outdoor not via
water trap, insulated pipe if in cold area)
5. for internal control: is aligned with parallel temperature curves for the
property (rec. 3
°
C higher curve for supply temperature in Climatix than in
the property)
For detailed wiring instructions, refer to the Order specific Control Schedule, for
communication settings, refer to New EcoHeater, Quick Start Guide for Climatix,
and for connection instructions, refer to New EcoHeater Assembly Instructions at
Heat pump start procedure (via CAREL):
A.
IMPORTANT!
The compressor’s crankcase must warm up before
being started. Heating takes place automatically using an in-built
heating coil when the compressor is connected to the power supply.
Heating time depends on the ambient temperature. Heating can take
several hours.
When the underside of the compressor feels warm, it may be started.
B. Allow the compressor to start as follows
Main Menu
1×
1×
1×
2×
On/Off Unit
IV Produkt
%
087
Demand:
083%
Status: UnitOn
Inv
ON
%
087
IV Produkt
Demand:
083%
Status: UnitOn
Inv
ON
Unit On/Off
Unit On/Off