Operation and Maintenance Instructions
NEW EcoCooler
DSKE180401.00.EN
Page 13
Continuous product development may give rise to specification changes without notice.
4.3 Cooling status
Unit incl. control (Climatix code MX)
Status information can be read on the Climatix display (Main menu > Unit >
Cooling). The following will be presented:
Climatix
Value
Explanation
Cooling unit status
UnitOn Status of cooling unit
Cooling
x% Cooling load from Climatix cooling regu-
lator.
Freq. inv. output
x.x% Frequency to the compressor.
Compr. no
Comp1
Compr. Sum alarm
Normal
Alarm management
> The alarm is displayed if there is a fault
with the inverter or compressor. In the
event of an alarm, see “Alarm information
for inverter and compressor” page 18.
****************************************
Compressor C1
On/Off Compressor operating mode.
Suction gas temp C1
x.x°C Measured suction gas temp.
Evaporation temp C1
x.x°C Calculated evaporation temp based on
low pressure.
Low pressure C1
x.x bar Relative pressure from low pressure sen-
sor.
Overheating C1
x.xK Measured overheating.
High pressure C1
x.x bar Relative pressure from high pressure sen-
sor.
Expansion valve 1
x.x% Expansion valve position.
Condensation temp C
x.x°C
Hot gas temperature
x.x°C Temperature of output from compressor
Liquid line tempera-
ture
x.x°C
Temperature downstream of condenser
Supercooling
x.x°C Measured supercooling