WARNING!!! The Fault Wizard produces a high-voltage electrical discharge that is potentially LETHAL. Only
personnel trained in the safe handling and operation of high voltage electrical devices are allowed to use this
device. All company, local and federal rules shall apply when using this piece of equipment.
Operators must fully read and understand the Fault Wizard operation manual before using. This Guide
is to be considered a reminder page only and does not include all instructions, cautions and procedures.
General Connection Diagram:
Wearing properly rated
high-voltage electrical gloves
are mandatory while
operating this device.
Display Information:
____________________________________________________________________________________________________________
Power Supply:
Always
TURN
Power Switch to
Off
when not in use and when working with clips.
The unit can only be operated from DC. If both battery sources are low, the battery must be
recharged before the unit can be used again.
Lethal Voltage is possible any time unit is on, use caution and follow all safety protocols!
____________________________________________________________________________________________________________
Finding Distance to Open Point:
Always
PRESS
the
LV TDR
button first to display the Reflection Distance (RD) to the open point of the
circuit or cable under test. Read display for distance to the open point. When shooting through transformers,
this could be:
1.
The end of multiple cable runs,
2.
An elbow that has blown off a transformer,
3.
Or an open in a conductor where all of the strands are burnt in half.
LV TDR
RT: OP
Battery Voltage
Reflection Type- SH-Short, OP- Open,
Flashing RF- Resistive Fault
Charge Voltage
Reflection Distance
(in Feet)
Velocity of
Propagation (VP)
HV Return Lead
Ground Lead
HV Lead
Insert Probe
Feed-Thru Bushing
Concentric Neutral